Date |
Text |
2005-11-22 00:00:00 | DENIED:BUILDING 10 / 2001 FBC |
| 1.PLAN SHEET A-0.0.0 PRODUCT |
| INFORMATION INDICATES TYPE VI, |
| UNPROTECTED SPRINKLERED.PLEASE |
| INDICATE WHICH SYSTEM WILL BE UTILIZED - |
| (13, 13R, 13D, ETC).PLEASE NOTE, |
| ADDITIONAL COMMENTS MAY BE GENERATED BY |
| THE RESPONSE GIVEN. |
| |
| 2.PLAN SHEET M1 INDICATES EXHAUST DUCT |
| PENETRATING FIRE RATED WALLS.PLEASE |
| SHOW COMPLIANCE WITH 2001 FMC 607.1.3 #3 |
| ITEMS 1 THROUGH 4. |
| |
| 3.PLAN SHEET M1 UNIT #88 R/A JUMPER |
| FROM THE GUEST SUITE IS NOT SIZED |
| PROPERLY.R/A SHOULD BE A MINIMUM OF |
| 12".PLEASE REVISE. |
| |
| 4.R/A TRANSFER GRILLES ARE NOT SIZE |
| PROPERLY.PLEASE REFERENCE 2001 FMC |
| 601.4 EXCEPTION #2 & 3 AND SIZE GRILLES |
| ACCORDINGLY. |
| |
| 3.PLAN SHEET M3 THE DRYER EXHAUST |
| DUCTS EXCEED THE 25FT REQUIREMENT WITH |
| REDUCTIONS FOR THE 90'S PER 2001 FMC |
| 504.6. |
| |
| 5.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH 2001 FMC |
| TABLE 403.3. |
| |
| 6.PLEASE PROVIDE DETAIL FOR THE AHU |
| LOCATED IN THE CLOSET.PLEASE NOTE, |
| MECHANICAL CLOSET SHALL COMPLY WITH 2001 |
| FMC 603.9 & 610.1.ABC.3.7 OF CHAPTER 13 |
| OF THE 2001 FBC. |
| |
| 7.CONDENSATE SHALL TERMINATE A MINIMUM |
| OF 12" AWAY FROM THE BUILDING STRUCTURE |
| PER 2001 FBC 1503.4.4. |
| |
| 8.AUXILIARY DRAIN PAN WITH OVERFLOW |
| PROTECTION REQUIRED PER 2001 FMC |
| 307.2.3. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561)805-6719. |