Plan Review Notes
Plan Review Notes For Permit 05091410
Permit Number 05091410
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-07 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED PROJECT APPEARS TO
 COMPRISE MORE THAN ONE PARCEL. PLEASE
 SUBMIT A COPY OF THE REPLAT.
  
 3) IN ORDER TO DETERMINE THE PERCENTAGE
 OF WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600, SUBMIT A SURVEY INDICATING
 THE LOCATIONS OF THE ASSUMED PROPERTY
 LINES BETWEEN THE BUILDINGS.
  
 4) PROVIDE AN AREA CALCULATION TABLE
 LISTING THE FLOOR AREA BREAKDOWNS BY
 FLOOR FOR EACH UNIT AND THE TOTALS FOR
 ALL FOUR UNITS.
  
 5) THE FBC DOES NOT ALLOW HEIGHT AND
 AREA INCREASES FOR NFPA 13R SPRINKLER
 SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D).
 SPECIFY THE TYPE OF SPRINKLER SYSTEM ON
 THE PLANS. MUST BE A FULL NFPA 13 SYSTEM
 FOR HEIGHT INCREASE. SUBMIT FIRE
 SPRINKLER PLANS PER FBC 104.3.1.1.
  
 6) FBC 2504.4.1 AND GA 216 REQUIRE WOOD
 FURRING TO BE NOT LESS THAN 3/4" X
 1-1/2" ACTUAL SIZE. ALSO, THE SURFACE
 CAN NOT VARY MORE THAN 1/8" FROM THE
 PLANE OF ADJACENT FURRING MEMBERS.
 DETAIL 1 ON A10.0.0 SHOWS THE FURRING
 ATTACHED OVER 3/4" POLYSTYRENE. PLEASE
 REVISE DETAIL TO COMPLY WITH CODE.
  
 7) SPECIFY THE INSULATION THAT WILL BE
 USED IN THE FLOOR/CEILING ASSEMBLY ABOVE
 THE GARAGE.
  
 8) THE GUTTER DOWNSPOUTS ARE REQUIRED TO
 DISCHARGE ONE FOOT AWAY FROM THE
 STRUCTURE PER FBC 1503.4.4.
  
 9) SHOW COMPLIANCE WITH FBC MECH. TABLE
 403.3 FOR REQUIRED OUTDOOR AIR
 VENTILATION AT GARAGES OF 100 CFM PER
 CAR.
  
 10) ON SHEET A-4.8.1 TWO BEDROOMS ARE
 LABELED BEDROOM #2.
  
 11) SPECIFY THE EXTERIOR FINISH AT THE
 UNDERSIDE OF THE BAY WINDOW SHOWN ON
 A-7.1.2. SPECIFY THE EXTERIOR SHEATHING,
 LATH AND STUCCO. NOTE: SEE ASTM C 926
 FOR REQUIRED STUCCO THICKNESS.
  
 12) ASTM C 926 REQUIRES 7/8" OF STUCCO
 WHEN APPLIED VERTICALLY ON METAL PLASTER
 BASE OVER SOLID BASE. PLEASE REVISE NOTE
 #46 FOR SECTION 4 ON A-7.0.2.
  
 13) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE. THIS IS THE VERTICAL DISTANCE
 FROM FINISHED GRADE TO THE A POINT AT
 THE AVERAGE HEIGHT OF THE ROOF.
  
 14) SUBMIT SHOP DRAWINGS FOR THE BALCONY
 GUARDRAILS. SPECIFY ATTACHMENTS, SPACING
 OF INTERMEDIATE RAILS, ETC.
  
 15) SPECIFY THE METHOD OF ATTACHMENT FOR
 THE ROOF TILES. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED HAS AN ATTACHMENT
 RESISTANCE MOMENT OF 24.5 FT-LBF FOR
 MORTAR SET TILE. FOR 140 MPH EXPOSURE B
 WITH 40FT MRH, THE REQUIRED MOMENT IS
 28.3 FT-LBF. PLEASE REVISE ROOF TILE
 DETAILS TO COMPLY WITH CODE.
  
 16) UL ASSEMBLY U 906 HAS A 2 HOUR FIRE
 RATING NOT ONE HOUR AS SPECIFIED ON THE
 PLANS FOR WALL TYPES IN DETAILS 2 AND 6
 ON A-10.00.
  
 17) SPECIFY DRAFTSTOPPING IN THE ROOF
 OVERHANGS IN LINE WITH THE TENANT
 SEPARATION WALLS AS REQUIRED BY FBC
 2305.2.3.
  
 18)705.7.1 JOINTS INSTALLED IN OR
 BE- TWEEN FIRE RESISTANT WALLS, FIRE
 RESIS- TANT FLOORS OR FLOOR/ CEILING
 ASSEMBLIES AND FIRE RESISTANT ROOFS OR
 ROOF/ CEILING ASSEMBLIES SHALL BE
 PROTECTED BY AN APPROVED FIRE RESISTANT
 JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A PERIOD NOT LESS
 THAN THE REQUIRED FIRE RESISTANCE RATING
 OF THE WALL, FLOOR OR FLOOR IN OR
 BETWEEN WHICH IT IS INSTALLED. SPECIFY
 THE JOINT SYSTEM AT THE TOP OF THE
 TENANT SEPARATION WALLS.
  
 19) DETAIL 17 ON A-10 DOES NOT
 CORRESPOND TO GA ASSEMBLY FC 5517
 SPECIFIED ON SHEET A 10.2.0.
  
 20) SUBMIT SIGNED AND SEALED TRUSS
 LAYOUTS AND DRAWINGS THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD FOR THE STRUCTURE.
  
 21) THE UPLIFT LOAD VALUES LISTED IN THE
 TRUSS ANCHOR SCHEDULE ON S-3 FOR THE
 SIMPSON HETAL 16 & 20 ARE INCORRECT.THE
 ONE THIRD STRESS INCREASE FOR STEEL
 CALCULATIONS IS NO LONGER ALLOWED. SEE
 THE 2005 SIMPSON CATALOG.
  
 22) THE HUGHES "USC" CONNECTORS ALSO
 HAVE INCORRECT UPLIFT VALUES. HUGHES WAS
 PURCHASED BY USP SEVERAL YEARS AGO AND
 IS LONGER IN BUSINESS. SEE THE 2005 USP
 CATALOG FOR VALUES. UPDATE THE TRUSS
 ANCHOR SCHEDULE.
  
 23) UNDER KEY NOTES/ LEGEND ON A-4.0 AND
 OTHER SHEETS REFERENCE IS MADE TO SHEET
 A-13 FOR THE WALL TYPES. HOWEVER, THERE
 IS NO SHEET A-13.
  
 24) THE ENERGY CALCULATIONS CONTAIN
 SEVERAL ERRORS. THESE ARE CONSIDERED
 MULTIFAMILY NOT SINLE FAMILY. THE
 ADJACENT WALL AT THE GARAGE IS METAL
 FRAME AND THE CEILING INSULATION IS
 SPECIFIED AS R-20 ICYENE.
  
 25)PROVIDE MANUFACTURER'S SPECIFICATIONS
 FOR THE ICYENE INSULATION.
  
 26) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 FLORIDA COVER SHEETS FOR ALL PRODUCT
 APPROVALS. IN ADDITION TO THE COVERSHEET
 THE INSTALLATION INSTRUCTIONS OR PRODUCT
 EVALUATION AS LISTED ON THE STATE
 WEBSITE IS ALSO REQUIRED. TWO (2) COPIES
 ARE REQUIRED.
  
 27) SUBMIT STATE PRODUCT APPROVALS FOR
 THE TRUSS CONNECTORS.
  
 28) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS HAS THE INFO FROM THE FIXED
 GLASS WINDOWS ATTACHED TO THE NOA
 COVERSHEET.
  
 29) THE DESIGN PRESSURES LISTED IN THE
 GARAGE DOOR PRODUCT APPROVALS DO NOT
 MEET THE PRESSURES SPECIFIED ON THE
 PLANS. SEE S-6.
  
 30) SUBMIT MANUFACTURER'S SPECS. FOR THE
 DOOR CLOSERS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714