2006-06-06 00:00:00 | PROVISO:2001 FBC/BUILDING 9/5 UNITS |
| |
| PLEASE REVISE PLANS TO REFLECT THE |
| IMPLEMENTATION OF PROVISO'S. |
| |
| 1.PLAN SHEET M0.1 THE AHU MOUNTING |
| DETAIL, NOTE 15 STATES "NO COMBUSTIBLES |
| ALLOWED IN MECHANICAL CLOSET" AS THIS IS |
| USED AS A RETURN AIR PLENUM.THE DOOR |
| SCHEDULE INDICATED ON A-4.7.1 SHOWS A |
| WOOD LOUVERED DOOR TO THE AHU CLOSET. |
| PLEASE VERIFY WITH THE DOOR MANFACTURE |
| THAT THIS MEETS THE 25 FLAME/50 SMOKE |
| INDEX SPECIFIED IN 2001 FMC 602.21. |
| |
| 2.OUTSIDE AIR CALCULATIONS INDICATED |
| ON PLAN SHEET M0.1 ARE BASED ON |
| INFILTRATION RATES.THE INFILTRATION |
| RATES ARE THE "MAXIMUM" ALLOWED BY CODE |
| & MAY NOT BE A "TRUE/ACTUAL" RATE. |
| PLEASE PROVIDE CALCS IN ACCORDANCE WITH |
| 2001 FMC 402.2., 402.2.1 OR TABLE 403.3. |
| PLEASE NOTE, 6" O.A. DUCT IS INDICATED |
| ON PLAN SHEET M2.PLEASE REMOVE FROM |
| THE PLAN IF THIS IS NOT BEING INSTALLED. |
| |
| 3.SPECIFIC DRYERS ARE TO BE INSTALLED |
| BY FINAL INSPECTION. |
| |