Plan Review Notes For Permit 05091406 |
Permit Number |
05091406 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-24 00:00:00 | ********DENIED********************* | | | | 1) ON SHEET A-0.0.0 UNDER GOVERNING CODE | | IDENTIFY LIFE SAFETY CODE AS NFPA 101 | | 2000 EDITION, WHEN IT SHOULD BE NFPA 101 | | LIFE SAFETY CODE 2003 EDITION. | | | | 2) MULTI-PURPOSE FIRE EXTINGUISHERS ARE | | REQUIRED FOR EACH UNITS. | | | | 3) SEPARATE SHOP DRAWINGS AND PERMIT ARE | | REQUIRED FOR FIRE SPRINKLER SYSTEM. | | | | 4) THE FLOW AND TAMPER SWITCHES ARE | | REQUIRED TO BE MONITORED BY A FIRE ALARM | | SYSTEM UL CERTIFIED FOR CENTRAL STATION | | SERVICES. SEPARATE SHOP DRAWINGS AND | | PERMIT ARE REQUIRED FOR FIRE ALARM | | SYSTEM. | | | | 5) AN ADDRESS IS REQUIRED FOR EACH UNIT, | | AND SHALL BE AT LEAST 3" IN HEIGHT AND | | CONTRASTING TO BACKGROUND. | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | 561-804-4754 |
|