2006-01-24 00:00:00********DENIED*********************
  
 1) ON SHEET A-0.0.0 UNDER GOVERNING CODE
 IDENTIFY LIFE SAFETY CODE AS NFPA 101
 2000 EDITION, WHEN IT SHOULD BE NFPA 101
 LIFE SAFETY CODE 2003 EDITION.
  
 2) MULTI-PURPOSE FIRE EXTINGUISHERS ARE
 REQUIRED FOR EACH UNITS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMIT ARE
 REQUIRED FOR FIRE SPRINKLER SYSTEM.
  
 4) THE FLOW AND TAMPER SWITCHES ARE
 REQUIRED TO BE MONITORED BY A FIRE ALARM
 SYSTEM UL CERTIFIED FOR CENTRAL STATION
 SERVICES. SEPARATE SHOP DRAWINGS AND
 PERMIT ARE REQUIRED FOR FIRE ALARM
 SYSTEM.
  
 5) AN ADDRESS IS REQUIRED FOR EACH UNIT,
 AND SHALL BE AT LEAST 3" IN HEIGHT AND
 CONTRASTING TO BACKGROUND.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL