Plan Review Notes
Plan Review Notes For Permit 05091406
Permit Number 05091406
Review Stop E
Sequence Number 1
Notes
Date Text
2005-10-17 00:00:00********* UNSAT *********
  
  
 1)NOTE: PLEASE SEE PROJECT IS SUBMITTED
 AS CONDO'S YET ELECTRICALSERVICES
 PROVIDED IS SHOWN AS EACH WOULD BE A
 TOWNHOUSE (FEE SIMPLE).
 PLEASE SEE WATER SERVICE SHOWS
 MULTI-FAMILY BLDG.
 PLEASE KNOW, IF THESE AS MULTI-FAMILY
 CONDO BLDGS; ONE SERVICE FOR EACH BLDG
 IS PERMITTED,230.2,230.70MAINS WILL BE
 REQUIRED TO BE GROUPED PER 230.72.
 MCB'S SHOWN IN EACH GARAGE PANEL IS
 PERMITTED.
 PLEASE ADJUST SERVICE FOR BLDG.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS ARE SHOWN FOR EACH PANEL,
 BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW
 SERVICE).
  
 3)NOTE: PLEASE CLARIFY LOCATION OF
 DISHWASHER RECEPT. APPEARS TO BE SHOWN
 BEHIND UNIT? THIS IS ONLY A NOTE:
  
 4))NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
  
  
 5)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52D FOR BATH RM(S). WHICH REQUIRE
 GFI TO BE WITHIN 3' OF LAV /SINK EDGE.
 PLEASE EITHER ADD ON OR MOVE EXISTING TO
 CENTER OF SINKS.
  
 6)NOTE: PLEASE SEE LOCATION OF A
 RECESSED LT FIXTURE IN CLOSET
 WASHER/DRYER LOCATION. THESE LOCATIONS
 TYPICALLY CONTAIN SHELVING ABOVE THE
 WASHER/DRYER'S. PLEASE SEE 410.8 FOR MIN
 CLEARENCE FROM LT AND FIXTURE TYPES.
 (WALL MOUNT)? AS SHOWN IN OTHER CLOSETS?
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS NEEDS
 TO BE SHOWN ABOVE THE GEN. KT/RECEPT
 LOADS. THIS SHOULD BE ABOVE THE FIGURED
 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: PLEASE LIST ALL THE REQUIRD ARC
 FAULT PROTECTED CIRCUITS AS REQUIRED PER
 2002 210.12
 PLEASE KNOW, SD'S ARE BEING SHOWN
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT,
 THIS IS OK, HOWEVER PLEASE KNOW, THIS
 WOULD ALSO REQUIRE ARC FAULT PROTECTION
 FOR THIS ADDITIONAL CIRCUIT.
 THIS IS ONLY A NOTE:
  
 9)NOTE: PLEEASE SEE NFPA-72 (2002)
 EDITION,11.8.3.5.
 PLEASE PLACE NOTE ON PLANS WHICH STATES
 LOCATIONS OF SD'S TO BE A MIN OF 3' FROM
 BATH(S) AND KITCHEN DOORS AND 20' FROM
 KITCHEN COOKING APPLIANCES.
 ** PLEASE SEE EXCEPTION TO 20' FROM
 COOKING WITH TYPE OF SD USED.**
 PLEASE SEE PLANS SHOWS A SD IN KITCHEN
 AREA AT THIS TIME.
  
 10)NOTE: PLEASE SEE MECHANICAL NOTES
 PERTAINING TO "DRYER BOOSTER FANS".
 AS PER MECHANICAL THESE MAY NOT BE
 PERMITTED AND ANY COMMENT THEY MAY HAVE
 WILL DIRECTLY AFFECT ELECTRICAL PLANS.
 THIS IS A NOTE, AS IT IS NOT AN NEC
 ISSUE.
 PLEASE SEE ALL SYSTEMS DO HAVE BE
 LISTED.110.3,90.7
 THIS MAY OR MAY NOT APPLY, AS NO BF'S
 ARE SHOWN FOR UNITS "C" AND "D"
  
 11)NOTE: PLEASE VERIFY OCP FOR AHU HEAT,
 PER 424.3B, MIN 125%.
  
 12)NOTE:PLEASE SEE RECEPT FOR LV
 TRANSFORMER MAY NOT BE LOCATE DIN
 CLOTHES CLOSET IN CLOSE PROXIMITY TO
 EASILY IGNITIBLE MATERIALS.240.24D
 RECEPT MAY BE PLACE ABOVE DOOR OR MOVED
 OUT OF CLOSET.
  
 13)NOTE: PLEASE SEE PLANS DO NOT
 INDICATE ANY ACCESIBLITY TO GFI RECEPTS
 SHOWN FOR JACUZZI/WHIRLPOOL TUB.
  
 14)NOTE: PLEASE SEE 406.2B,210.21B3&4
 WHICH REQUIRES THE MAX OCP FOR A 50A
 RANGE RECEPT TO BE 50A'S. PLEASE SEE A
 2P-60A BRKR IS SHOWN.
  
 15)NOTE: PLEASE PROVIDE AREA AND ROOM
 DESIGNATIONS ON PLANS. PLEASE SEE SOME
 ARE MISSING.
 THIS WILL ALSO BE REQUIRED TO DETERMINE
 CIRCUITING FOR DINING AREAS.
  
 16)NOTE: PLEASE SEE PLANS REFERENCE THE
 2000 NFPA 101, WHEN AS OF JAN 1ST 2005,
 THE 2003 NFPA-101 IS IN EFFECT.
  
 ** PLEASE KNOW, MANY ITEMS HAVE BEEN
 REDLINED ON PLANS FOR LOCATIONS OF
 NOTES.
  
 ** PLEASE KNOW, A REVIEW OF MAIN
 ELECTRICAL SERVICECAN NOT BE DONE AT
 THIS TIME, AS SERVICE WILL BE CHANGING.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE THIS MAY BE CONSIDERED A
 "THRESHOLD" PROJECT. IF SO, THREE SETS
 OF PLANS WILL BE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved