2006-06-26 00:00:00 | PROVISO:2001 FBC/BUILDING 8/5 UNITS |
| PLEASE REVISE PLANS TO REFLECT THE |
| IMPLEMENTATION OF THE PROVISO'S. |
| |
| COMMENT #3:BOOSTER FAN WAS DELETED |
| FROM TEH PLAN. SPECIFIC DRYER WAS CHOSEN |
| TO MEET CODE REQUIREMENT.PLEASE NOTE |
| SPECIFIC DRYER TO BE INSTALLED FOR FINAL |
| INSPECTION PER 2001 FMC 504.6. |
| |
| COMMENT #5:OUTSIDE AIR CALCUALTIONS |
| THAT ARE INDICATED ON PLAN SHEET M0.1 |
| ARE BASED ON INFILTRATION RATE.THE |
| INFILTRATION RATES ARE THE "MAXIMUM" |
| ALLOWED BY CODE AND MAY NOT BE A "TRUE" |
| RATE.PLEASE PROVIDE CALCULATIONS IN |
| ACCORDANCE WITH 2001 FMC 402.2, 402.2.1 |
| OR TABLE 403.3.PLEASE NOTE, 6" OUTSIDE |
| AIR DUCT IS INDICATED ON PLAN SHEET M2. |
| PLEASE REMOVE FROM THE PLAN IF THIS WILL |
| NOT BE INSTALLED. |
| |
| COMMENT #8:PLAN SHEET M0.1 AHU DETAIL |
| NOTE 15 INDICATES NO COMBUSTIBLES |
| ALLOWED IN THE AHU CLOSET WHICH SERVES |
| AS THE RETURN AIR PLENUM.THE LOUVERED |
| DOOR LISTED ON PLAN SHEET A-4.0.2 IS |
| CONSTRUCTED OF WOOD.PLEASE NOTE, THE |
| DOOR & FRAME SHALL ALSO MEET THE 25 |
| FLAME/50 SMOKE INDEX AS SPECIFIED IN |
| 2001 FMC 602.2.1. |
| |