Plan Review Notes For Permit 05091404 |
Permit Number |
05091404 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-15 00:00:00 | ***** UNSAT **** | | | | | | 1) NOTE: PLEASE SEE NO, SERVICE ENTRANCE | | CONDUIT OR SERVICE ENTRANCE CONDUCTORS | | ARE SHOWN ON RISER FROM FPL TO 1000A | | SERVICE MAIN. | | PLEASE SEE SEC'S ARE NOTED IN FAULT | | CURRENT CALCS ONLY. | | PLEASE ALSO VERIFY SIZE WHICH MAY ALSO | | AFFECT NOTE #2. | | | | 2) NOTE: PLEASE SEE #4 GEC SHOWN, WHERE | | A 3/0 MIN IS REQUIRED PER 250.66, BASED | | ON THE SEC'S SHOWN IN FAULT CURRENT | | CALCS. | | | | 3) NOTE: PLEASE SEE KEY PLAN INDICATE | | THIS BEING A 5 UNITS BUILDING AND PLANS | | IN TITLE BLOCKS ALSO INDOCATE THIS AS A | | FIVE UNIT BLDG, HOWEVER PLEASE SEE RISER | | SHOWN , ONLY PROVIDES SERVICE FOR FOUR | | UNITS. | | PLEASE CORRELATE AND ADJUST AS NEEDED. | | 215.5 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|