Plan Review Notes
Plan Review Notes For Permit 05091404
Permit Number 05091404
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-15 00:00:00***** UNSAT ****
  
  
 1) NOTE: PLEASE SEE NO, SERVICE ENTRANCE
 CONDUIT OR SERVICE ENTRANCE CONDUCTORS
 ARE SHOWN ON RISER FROM FPL TO 1000A
 SERVICE MAIN.
 PLEASE SEE SEC'S ARE NOTED IN FAULT
 CURRENT CALCS ONLY.
 PLEASE ALSO VERIFY SIZE WHICH MAY ALSO
 AFFECT NOTE #2.
  
 2) NOTE: PLEASE SEE #4 GEC SHOWN, WHERE
 A 3/0 MIN IS REQUIRED PER 250.66, BASED
 ON THE SEC'S SHOWN IN FAULT CURRENT
 CALCS.
  
 3) NOTE: PLEASE SEE KEY PLAN INDICATE
 THIS BEING A 5 UNITS BUILDING AND PLANS
 IN TITLE BLOCKS ALSO INDOCATE THIS AS A
 FIVE UNIT BLDG, HOWEVER PLEASE SEE RISER
 SHOWN , ONLY PROVIDES SERVICE FOR FOUR
 UNITS.
 PLEASE CORRELATE AND ADJUST AS NEEDED.
 215.5
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]