Date |
Text |
2005-11-30 00:00:00 | DENIED:BUILDING 7 / 2001 FBC |
| 1.PLAN SHEET A-0.0.0 PROJECT |
| INFORMATION INDICATES TYPE VI, |
| UNPROTECTED SPRINKLERED.PLEASE |
| INDICATE WHICH SYSTEM WILL BE UTILIZED |
| (13, 13R, 13D?).PLEASE NOTE, |
| ADDITIONAL COMMENTS MAY BE GENEERATED BY |
| THE RESPONSES GIVEN. |
| |
| 2.PLAN SHEET A-4.6.1 KEY NOTES/LEGEND, |
| ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| PLAN SHEET A-13 WAS NOT SUBMITTED FOR |
| REVIEW. |
| |
| 3.PLAN SHEET M0.1 THE EQUIPMENT |
| SCHEDULE INDICATES AHU-1 AS A 5 TON |
| UNIT.PER 2001 FMC 606.2.1, SYSTEMS |
| WITH THE DESIGN CAPACITY SHALL HAVE DUCT |
| SMOKE DETECTOR.NOTE #2 INDICATES AREA |
| SMOKE DETECTORS UPON ACTIVATION WILL |
| SHUT DOWN AHU.THE ELETRICAL PLANS DO |
| NOT REFLECT THIS.PLEASE CORRELATE. |
| |
| 4.PLEASE CLARIFY RATING OF THE WALL |
| SEPARATING THE GARAGE & THE RESIDENCE, |
| DOES THE RATING OF THE WALL CONTINUE TO |
| THE SLAB OR STOP AT THE RATED CEILING? |
| |
| 5.PLAN SHEET M1 INDICATES EXHAUST DUCT |
| PENETRATING RATED WALL.DUCT SHALL |
| COMPLY WITH 2001 FMC 607.1.3 #3 ITEMS 1 |
| THROUGH 4. |
| |
| 6.PLAN SHEET M3 DRYER EXHAUST EXCEEDS |
| THE 25FT MAXIMUM LENGTH WITH A 5FT |
| REDUCTION FOR EACH 90 PER 2001 FMC |
| 504.6.PLEASE NOTE, A SPECIFIC DRYER |
| WITH THE CAPACITY GREATER THAN THE 25FT |
| PER MANUFACTURERS SPECIFICATIONS MAY BE |
| USED.PLEASE PROVIDE DRYER SUBMITTALS. |
| |
| 7.R/A TRANSFER GRILLES SHALL BE SIZED |
| IN ACCORDANCE WTIH 2001 FMC 601.4 |
| EXCEPTION 2 & 3. |
| |
| 8.MECHANICAL CLOSET SHALL BE |
| CONSTRUCTED IN ACCORDANCE WITH 2001 FMC |
| 603.9.NO COMBUSTIBLES ALLOWED PER 2001 |
| FMC 602.2.1. |
| |
| 9.PLEASE PROVIDE DETAIL FOR THE AHU |
| CLOSET. |
| |
| 10.PLEASE PROVIDE DETAIL FOR THE |
| MOUNTING OF THE CONDENSING UNIT PER 2001 |
| FMC 301.13. |
| |
| 11.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH 2001 FMC |
| TABLE 403.3. |
| |