Date |
Text |
2005-10-17 00:00:00 | ********* UNSAT ********* |
| |
| |
| 1)NOTE: PLEASE SEE PROJECT IS SUBMITTED |
| AS CONDO'S YET ELECTRICALSERVICES |
| PROVIDED IS SHOWN AS EACH WOULD BE A |
| TOWNHOUSE (FEE SIMPLE). |
| PLEASE SEE WATER SERVICE SHOWS |
| MULTI-FAMILY BLDG. |
| PLEASE KNOW, IF THESE AS MULTI-FAMILY |
| CONDO BLDGS; ONE SERVICE FOR EACH BLDG |
| IS PERMITTED,230.2,230.70MAINS WILL BE |
| REQUIRED TO BE GROUPED PER 230.72. |
| MCB'S SHOWN IN EACH GARAGE PANEL IS |
| PERMITTED. |
| PLEASE ADJUST SERVICE FOR BLDG. |
| |
| 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| AIC RATINGS ARE SHOWN FOR EACH PANEL, |
| BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW |
| SERVICE). |
| |
| 3)NOTE: PLEASE CLARIFY LOCATION OF |
| DISHWASHER RECEPT. APPEARS TO BE SHOWN |
| BEHIND UNIT? THIS IS ONLY A NOTE: |
| |
| 4))NOTE: PLEASE SEE RECEPTS SERVING |
| KITCHEN COUNTERSPACE TO MEET 210.52C- |
| SEC'S 1,2,3,4 AND 5 |
| |
| 5)NOTE: PLEASE SHOW OUTLET SPACING PER |
| 210.52D FOR GFI REQUIRED WITHIN 3' OF |
| SINK EDGE. PLEASE EITHER ADD ONE OR MOVE |
| EXISTING IN BETWEEN BOTH LAV'S. |
| |
| 6)NOTE: PLEASE VERIFY WASHER AND DRYER |
| INDICATE DON PANEL SCHEDULE. PLANS SHOW |
| DRYER AND NOT WASHER INUNIT. |
| |
| 7 )NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS NEEDS |
| TO BE SHOWN ABOVE THE GEN. KT/RECEPT |
| LOADS. THIS SHOULD BE ABOVE THE FIGURED |
| 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 8)NOTE: PLEASE LIST ALL THE REQUIRD ARC |
| FAULT PROECTED CIRCUITS AS REQUIRED PER |
| 2002 210.12 |
| PLEASE KNOW, SD'S ARE BEING SHOWN |
| CIRCUITED TO KITCHEN LIGHTING CIRCUIT, |
| THIS IS OK, HOWEVER PLEASE KNOW, THIS |
| WOULD ALSO REQUIRE ARC FAULT PROTECTION |
| FOR THIS ADDITIONAL CIRCUIT. |
| THIS IS ONLY A NOTE: |
| |
| 9)NOTE: PLEEASE SEE NFPA-72 (2002) |
| EDITION,11.8.3.5. |
| PLEASE PLACE NOTE ON PLANS WHICH STATES |
| LOCATIONS OF SD'S TO BE A MIN OF 3' FROM |
| BATH(S) AND KITCHEN DOORS AND 20' FROM |
| KITCHEN COOKING APPLIANCES. |
| ** PLEASE SEE EXCEPTION TO 20' FROM |
| COOKING WITH TYPE OF SD USED.** |
| PLEASE SEE PLANS SHOWS A SD IN KITCHEN |
| AREA AT THIS TIME. |
| |
| 10)NOTE: PLEASE SEE MECHANICAL NOTES |
| PERTAINING TO "DRYER BOOSTER FANS". |
| AS PER MECHANICAL THESE MAY NOT BE |
| PERMITTED AND ANY COMMENT THEY MAY HAVE |
| WILL DIRECTLY AFFECT ELECTRICAL PLANS. |
| THIS IS A NOTE, AS IT IS NOT AN NEC |
| ISSUE. |
| PLEASE SEE ALL SYSTEMS DO HAVE BE |
| LISTED.110.3,90.7 |
| THIS COMMENTS MAY OR MAY NOT APPLY. NO |
| BF'S SHOWN IN "C" AND "D" UNITS |
| |
| 11)NOTE: PLEASE VERIFY OCP FOR AHU HEAT, |
| PER 424.3B, MIN 125%. |
| |
| 12)NOTE:PLEASE SEE RECEPT FOR LV |
| PANEL, MAY NOT LOCATED IN AREA OF CLOSE |
| PROXIMITY TO EASILY IGNITIBLE MATERIALS. |
| 240.24D. PLEASE SEE RECEPT MAY BE ABOVE |
| DOOR , OR MUST BE REMOVED FROM ROOM. |
| |
| 13)NOTE: PLEASE SEE PLANS DO NOT |
| INDICATE ANY ACCESIBLITY TO GFI RECEPTS |
| SHOWN FOR JACUZZI/WHIRLPOOL TUB. |
| |
| 14)NOTE: PLEASE SEE 406.2B,210.21B3&4 |
| WHICH REQUIRES THE MAX OCP FOR A 50A |
| RANGE RECEPT TO BE 50A'S. PLEASE SEE A |
| 2P-60A BRKR IS SHOWN. |
| |
| 15)NOTE: PLEASE PROVIDE AREA AND ROOM |
| DESIGNATIONS ON PLANS. PLEASE SEE SOME |
| ARE MISSING. |
| THIS WILL ALSO BE REQUIRED TO DETERMINE |
| CIRCUITING FOR DINING AREAS. |
| |
| 16)NOTE: PLEASE SEE PLANS REFERENCE THE |
| 2000 NFPA 101, WHEN AS OF JAN 1ST 2005, |
| THE 2003 NFPA-101 IS IN EFFECT. |
| |
| ** PLEASE KNOW, MANY ITEMS HAVE BEEN |
| REDLINED ON PLANS FOR LOCATIONS OF |
| NOTES. |
| |
| ** PLEASE KNOW, A REVIEW OF MAIN |
| ELECTRICAL SERVICECAN NOT BE DONE AT |
| THIS TIME, AS SERVICE WILL BE CHANGING. |
| |
| PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| FROM OTHER TRADES WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| ** PLEASE SEE THIS MAY BE CONSIDERED A |
| "THRESHOLD" PROJECT. IF SO, THREE SETS |
| OF PLANS WILL BE REQUIRED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |