2005-11-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091396
 ADD: 3815 PASEO ANDALUSIA
 CONT: AAA ALUMINUM
 TEL: (561)533-9869
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FBC 104.2.1ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.PLEASE COMPLY.
  
 2) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLEASE PROVIDE THE TYPE OF ROOM THE
 WINDOWS ARE BEING REPLACED IN? NOTE
 IF THE 74"X50 5/8" OPENING IS ACTUALLY
 (2) 24 OPENINGS 37"X50.625", AND THIS IS
 A SLEEPING ROOM, THE WINDOWS DO NOT MEET
 THE REQUIRED 5.0 SQ FT OF CLEARVENT
 REQUIRED FOR EGRESS. THEY WOULD HAVE TO
 INCREASE THE WINDOW SIZE TO A 245 WINDOW
 WITH A MAXIMUM 5/8" SASH STOP.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  