Plan Review Notes
Plan Review Notes For Permit 05091390
Permit Number 05091390
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-23 00:00:001) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
  
 3) THE SLIDING GLASS DOOR/WALL PANELS
 AND
 ROOF PANELS NEEDS PRODUCT APPROVALS.
 ALSO THE STATE COVER SHEET WITH THE FL#
 IS REQUIRED FOR ALL PRODUCTS.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) FL.BLD CODE 104.2.1.1 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE, AND DELINATE THE TYPE OF
 ROOFING SYSTEM, MATERIALS,FASTENINGS
 REQUIREMENTS, FLASHING REQUIREMENTS AND
 WIND RESISTANCE RATING THAT ARE REQUIRED
 TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN
 ARCHITECT OR ENGINEER FOR THE SPECIFIC
 SITE MUST BE SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS.SHOW THE
 DIFFERENT ELEVATIONS OF THE STRUCTURE.
  
 6) FL.BLD CODE 2002.1 THE QUALITY,
 DESIGN,FABRICATION AND ERECTION OF
 ALUMINUM USED STRUCTURALLY IN BUILDINGS
 OR STRUCTURES SHALL COMFORM TO GOOD
 ENGINEERING PRACTICE, THE PROVISIONS OF
 THIS CHAPTER AND OTHER APPLICABLE
 REQUIREMENTS OF THES CODE.
  
 7) FL. BLD CODE 1604.6.1 THE DESIGN ROOF
 LIVE LOADS SHALL TAKE INTO ACCOUNT THE
 EFFECTS OF OCCUPANCY AND WATER BUT SHALL
 BE NOT LESS THAN THE MINIMUM ROOF LIVE
 OLADS AS SET FORTH IN TABLE 1604.6
  
 8) FL. BLD CODE 104.2.2 IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF
 THIS STATE REGULATING THE PRACTICE OF
 ARCHITECTURE OR ENGINEERING, THEN HE/SHE
 SHALL AFFIX HIS/HER OFFICIAL SEAL TO
 SAID DRAWINGS,SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY
 FLORIDA STATUTES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL (561)805-6726
 FAX (561)659-8026
 [email protected]
  
  
  
  
  