Plan Review Notes
Plan Review Notes For Permit 05091363
Permit Number 05091363
Review Stop B
Sequence Number 1
Notes
Date Text
2005-12-07 00:00:00 
  
 DENIED
  
 1) PROVIDE A NOTICE OF COMMENCEMENT
 RECORDED WITH THE CLERK OF COURT BEFORE
 A PERMIT CAN BE ISSUED
  
 2) PROVIDE VERIFICATION THAT POOL DECK
 MEETS THE REQUIREMENTS OF THE FOOTER
 TABLES IN THE ENGINEERING
  
 3) SPECIFY ON THE ENGINEERING ALL OF THE
 ATTACMENTS TO BE USED ON THIS
 INSTALLATION
  
 4) BEAM SPANS EXCEED THE SPANS SELECTED
 ON THE ENGINEERING SHEET
  
 5) COLUMN HEIGHT OF CENTER COLUMN
 EXCEEDS LENGTH ALLOWED UNLESS HEAVY IS
 SPECIFIED
  
 6) PROVIDE 2 COPIES OF ALL INFORMATION
 INCLUDING SCREEN DRAWINGS
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 (561)805-6716