Plan Review Notes For Permit 05091331 |
Permit Number |
05091331 |
|
Review Stop |
E |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2006-10-22 17:06:59 | **** UNSAT **** | | | | 1) NOTE: PLEASE SEE AHU KW RATING HEAT LOAD HAS BEEN | | INCREASED HOWEVER LOAD CALCUALITONS HAVE NOT BEEN | | UPDATED?? | | PLEASE SEE 220.31. | | PANEL"B". | | | | 2) NOTE: PLEASE SEE A PART OF A PANEL SCHEDULE IS BEING | | SHOWN JUST TO THE RIGHT OF THE LOAD CALCULATIONS, | | HOWEVER ARE NOT ON ANY PARTICULAR PANEL SCHEDULE. | | PLEASE REVISED AND ADJUST PLANS. | | 240.4, 310.16, 408.4. | | | | PLEASE SUBMIT THE ABOVE FOR CORRECTIONS. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER. | | EELCTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|