Plan Review Notes
Plan Review Notes For Permit 05091331
Permit Number 05091331
Review Stop E
Sequence Number 6
Notes
Date Text
2006-10-22 17:06:59**** UNSAT ****
  
 1) NOTE: PLEASE SEE AHU KW RATING HEAT LOAD HAS BEEN
 INCREASED HOWEVER LOAD CALCUALITONS HAVE NOT BEEN
 UPDATED??
 PLEASE SEE 220.31.
 PANEL"B".
  
 2) NOTE: PLEASE SEE A PART OF A PANEL SCHEDULE IS BEING
 SHOWN JUST TO THE RIGHT OF THE LOAD CALCULATIONS,
 HOWEVER ARE NOT ON ANY PARTICULAR PANEL SCHEDULE.
 PLEASE REVISED AND ADJUST PLANS.
 240.4, 310.16, 408.4.
  
 PLEASE SUBMIT THE ABOVE FOR CORRECTIONS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER.
 EELCTRICAL PLAN REVIEW