Plan Review Notes For Permit 05091331 |
Permit Number |
05091331 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-12-07 00:00:00 | *********** PROVISO/REVISION ********** | | | | PLEASE SEE COMMENTS FROM FIRST TWO | | REVIEWS AND NEW NOTES DUE TO CHANGES IN | | LOADS FOR POOL PANEL. | | | | 1)NOTE: PLEASE CORRELATE A/C LOADS. | | PLEASE SEE PANEL "B", WHICH INDICATES A | | 10KW HEAT STRIP, HOWEVER LOAD | | CALCULATIONS INDICATE 65% LOAD AT | | 9750VA?? | | 9750VA IS NOT 65% OF 10KW. | | 215.5 | | | | 2)NOTE: PLEASE SEE LOAD CALCUALTIONS FOR | | POOL PANEL NOW HAVE BEEN CHANGED AND | | CONTINUOUS LOAD FACTOR OF 125% HAS BEEN | | REMOVED?? | | PLEASE SEE 215.3,230.42 ETC, AND PLEASE | | ADJUST LOAD CALCULATIONS TO INCLUDE ALL | | CONTINUOUS LOADS AT 125%. | | PLEASE ALSO SEE TOTAL KVA LOAD SHOWN ON | | PANEL "B" DOES NOT CORRELATE WITH POOL | | PANEL. | | ONE SHOWS 13,270 AND THE OTHER 14,670? | | | | ** PLEASE MAKE THE ABOVE CORRECTIONS | | ALONG WITH ANY OTHER REVISIONS BEFORE | | ROUGH ELECTRICAL INSPECTION. | | PLANS MUST BE SUBMITTED FOR REVIEW, | | STAMPING AND ON JOBSITE FOR ROUGH. | | | | ONCE AGAIN, IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|