Plan Review Notes
Plan Review Notes For Permit 05091331
Permit Number 05091331
Review Stop E
Sequence Number 2
Notes
Date Text
2005-11-17 00:00:00******** UNSAT 2ND REVIEW *******
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED AND
 PLEASE SEE NEW NOTES DUE TO CHANGES
 MADE.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 OK, WATER HEATER
 REMOVED, GAS.
  
 3)NOTE: NOTE #3 NO,PLEASE SEE MIN OCP
 REQUIRED FOR POOL HEAT PUMP TO BE 125%.
 680.9
 THIS HAS NOT BEEN CHANGED
  
 4)NOTE: NOTE #4 NO, PLEASE INDICATE ALL
 CONTINUOUS LOADS AT 125%. (POOL PUMP,
 HEAT PUMP).
 PLEASE SEE 215.3,230.42 ETC.
 PLEASE SEE THE FINAL LOAD CALCULATION
 WAS REVISED HOWEVER NOT OCP, AND LOADS
 FOR INDIVIDUAL UNITS WERE NOT NOTED OR
 CHANGED.
 PLEASE SEE POOL PANEL HAD ALREADY SHOWN
 A LOAD AT 59.45A'S AND NOW LOAD EXCEEDS
 FEED FOR PANEL.
 THIS WAS MENTIONED ON PREVIOUS NOTES TO
 UPDATE FEEDER AND OCP, HOWEVER OCP STILL
 SHOWS A 60A FEED.
 CONDUCTORS WERE CHANGED.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE LOAD
 SHOWN FOR A/C LOADS ON PANEL "B" LOAD
 CALCUALTIONS STILL DO NOT CORRELATE.
 PLEASE SEE KVA HAS NOW CHANGED TO 10KW
 PLEASE CORRELATE AHU LOADS,
 PLEASE SEE NEW NOTE DUE TO INCREASE IN
 KW RATING.
  
 6)NOTE: NOTE #6 NO. PLEASE LIST ALL THE
 REQUIRED ARC FAULT PROTECTED CIRCUITS AS
 REQUIRED UNDER THE 2002 NEC. 210.12.
 SD'S,LTS, RECEPTS, FANS ETC ARE ALL
 REQUIRED TO HAVE ARC FAULT PROTECTION.
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE:NOTE #9 NO, PLEASE SEE 410.8
 FOR MINCLEARENCE REQUIRED FOR LT IN
 PANTRY.
 PLEASE KNOW, PANTRIES ARE LIKELY TO
 CONTAIN COMBUSTIBLES.
 PLEASE KNOW, IT IS NOTED THAT A NOTE ON
 PLANS NOW MENTIONS LT ABOVE ON CEILING,
 HOWEVER THIS DOES NOT CHANGE THE MIN
 CLEARENCE REQUIREMENTS FOR TYPE OF
 FIXTURE SHOWN.
 CLEARENCES FROM 410.8 GO ALL THE WAY TO
 THE CEILING.
  
 10)NOTE:NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK.
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE424.3B , NOW THAT KW
 RATING FOR AHU HAS NOW INCREASED TO
 10KW, THE MIN OCP SHALL BE SIZED @125%.
 PLEASE ALSO ADJUST MIN AWG ONCE OCP HAS
 BEEN INCREASED.
  
 2)NOTE: PLEASE SEE A NOTICE IS NOW GIVEN
 WITH RESPECT TO THE DESIGN PROFESSIONAL
 AND REPEAT COMMENTS.
 PLEASE SEE COPY OF FS 553.80(2)(B)
 ATTACHED.
 THIS IS ONLY A NOTE GIVEN AT THIS TIME.
  
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ** PLEASE SEE MOST OF THE ITEMS ABOVE
 HAVE BEEN REDLINED ON ONE SET OF PLANS
 FOR AREAS OF COMMENTS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  