Plan Review Notes
Plan Review Notes For Permit 05091331
Permit Number 05091331
Review Stop E
Sequence Number 1
Notes
Date Text
2005-10-06 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE MOVESMOKE DETECTOR IN
 MASTER BEDROOM AREA TO BE LOCATED WITH
 THE HIGHEST POINT OF THE CEILING. THIS
 IS REQUIRED TO BE WITH 12" OF THE
 HIGHEST POINT OF A FLAT CEILING.
 NFPA-72 11.8.3.5
  
 2)NOTE: PLEASE SEE WATER HEATER #2 AS
 LISTED ON PANEL SCHEDULE "A" COULD NOT
 BE LCOATED ON PLANS. PLEASE SHOW.
  
 3)NOTE: PLEASE SEE MIN OCP REQUIRED FOR
 POOL HEAT PUMP TO BE 125%.
 680.9
  
 4)NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125%. (POOL PUMP, HEAT PUMP).
 PLEASE SEE 215.3,230.42 ETC.
 PLEASE SEE POOL PANEL ALREADY SHOWS LOAD
 AT 59.45A'S.
 THIS PANEL, FEEDER, OCP ETC WILL BE
 REQUIRED TO BE INCREASED. PLEASE SEE
 PANEL MUST ALSO CONTAIN SPACE FOR FTURE
 LOAD. 90.8
 PLEASE FOLLOW THROUGH WITH LOAD
 CALCULATIONSON PANEL "B".
  
 5)NOTE: PLEASE CORRELATE AHU LOADS,
 PLEASE SEE LOAD CALCS FOR PANEL "B"
 SHOWS 6750 @65%?, YET PANEL SHOWS
 7500VA?
  
 6)NOTE: PLEASE LIST ALL THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRED
 UNDER THE 2002 NEC. 210.12.
 SD'S,LTS, RECEPTS, FANS ETC ARE ALL
 REQUIRED TO HAVE ARC FAULT PROTECTION.
  
 7)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO SUB
 PANELS.
 250.110,250.122 ETC.
  
 8)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LT FIXTURES ON PLANS WITH THE
 NUMBER OF FIXTURES INDICATED IN LOAD
 CALCULATIONS.
 215.5
  
 9)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE REQUIRED FOR LT IN PANTRY.
 PLEASE KNOW, PANTRIES ARE LIKELY TO
 CONTAIN COMBUSTIBLES.
  
 10)NOTE: PLEASE SEE PLANS APPEAR TO HAVE
 A GFI RECEPT MISSING ALONG KITCHEN
 COUNTERSPACE.
 PLEASE SEE 210.52C1
  
 11)NOTE: PLEASE SEE GDO'S ARE SHOWN ON
 PANEL SCHEDULES, HOWEVER THESE RECEPTS
 COULD NOT BE LOCATED ON PLANS.
  
 ** PLEASE SEE MOST OF THE ITEMS ABOVE
 HAVE BEEN REDLINED ON ONE SET OF PLANS
 FOR AREAS OF COMMENTS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  