Date |
Text |
2005-10-06 00:00:00 | *********** UNSAT ************ |
| |
| 1)NOTE: PLEASE MOVESMOKE DETECTOR IN |
| MASTER BEDROOM AREA TO BE LOCATED WITH |
| THE HIGHEST POINT OF THE CEILING. THIS |
| IS REQUIRED TO BE WITH 12" OF THE |
| HIGHEST POINT OF A FLAT CEILING. |
| NFPA-72 11.8.3.5 |
| |
| 2)NOTE: PLEASE SEE WATER HEATER #2 AS |
| LISTED ON PANEL SCHEDULE "A" COULD NOT |
| BE LCOATED ON PLANS. PLEASE SHOW. |
| |
| 3)NOTE: PLEASE SEE MIN OCP REQUIRED FOR |
| POOL HEAT PUMP TO BE 125%. |
| 680.9 |
| |
| 4)NOTE: PLEASE INDICATE ALL CONTINUOUS |
| LOADS AT 125%. (POOL PUMP, HEAT PUMP). |
| PLEASE SEE 215.3,230.42 ETC. |
| PLEASE SEE POOL PANEL ALREADY SHOWS LOAD |
| AT 59.45A'S. |
| THIS PANEL, FEEDER, OCP ETC WILL BE |
| REQUIRED TO BE INCREASED. PLEASE SEE |
| PANEL MUST ALSO CONTAIN SPACE FOR FTURE |
| LOAD. 90.8 |
| PLEASE FOLLOW THROUGH WITH LOAD |
| CALCULATIONSON PANEL "B". |
| |
| 5)NOTE: PLEASE CORRELATE AHU LOADS, |
| PLEASE SEE LOAD CALCS FOR PANEL "B" |
| SHOWS 6750 @65%?, YET PANEL SHOWS |
| 7500VA? |
| |
| 6)NOTE: PLEASE LIST ALL THE REQUIRED ARC |
| FAULT PROTECTED CIRCUITS AS REQUIRED |
| UNDER THE 2002 NEC. 210.12. |
| SD'S,LTS, RECEPTS, FANS ETC ARE ALL |
| REQUIRED TO HAVE ARC FAULT PROTECTION. |
| |
| 7)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTORS FROM MAINS TO SUB |
| PANELS. |
| 250.110,250.122 ETC. |
| |
| 8)NOTE: PLEASE CORRELATE THE NUMBER OF |
| RECESSED LT FIXTURES ON PLANS WITH THE |
| NUMBER OF FIXTURES INDICATED IN LOAD |
| CALCULATIONS. |
| 215.5 |
| |
| 9)NOTE: PLEASE SEE 410.8 FOR MIN |
| CLEARENCE REQUIRED FOR LT IN PANTRY. |
| PLEASE KNOW, PANTRIES ARE LIKELY TO |
| CONTAIN COMBUSTIBLES. |
| |
| 10)NOTE: PLEASE SEE PLANS APPEAR TO HAVE |
| A GFI RECEPT MISSING ALONG KITCHEN |
| COUNTERSPACE. |
| PLEASE SEE 210.52C1 |
| |
| 11)NOTE: PLEASE SEE GDO'S ARE SHOWN ON |
| PANEL SCHEDULES, HOWEVER THESE RECEPTS |
| COULD NOT BE LOCATED ON PLANS. |
| |
| ** PLEASE SEE MOST OF THE ITEMS ABOVE |
| HAVE BEEN REDLINED ON ONE SET OF PLANS |
| FOR AREAS OF COMMENTS. |
| |
| ** PLEASE BE SURE TO REMOVE ALL |
| OLD/VOIDED SHEETS FROM SETS AND AND ONLY |
| INSERT NEW REVISED SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |