Plan Review Notes For Permit 05091318 |
Permit Number |
05091318 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-10-04 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} ALL DRAWINGS SHALL BEAR THE NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | THE DESIGN. 104.2.1 FBC. | | IF A ARCHITECT OR THE ENGINEER WHO'S | | TITLE BLOCK APPEARS ON THE PLAN, COMPLY | | WITH ARTICLES 481 AND 471 RESPECTIVELY. | | | | 2} SUBMIT THE AIC CALCULATIONS FOR THE | | SERVICE AND INDICATE THE AIC RATING OF | | THE EQUIPMENT PER 110.9 & 10. | | | | 3}THE GROUNDING ELECTRODE SYSTEM NEEDS | | TO ORIGINATE FROM ONE POINT. THE RISER | | HAS TWO, ONE FROM THE METER AND ONE FROM | | THE PANEL. SEE 250.36(F) FOR LOCATION | | PERMITTED. | | | | 4} THE DINING ROOM CIRCUIT MUST COMPLY | | WITH 210.52(B)(1), 20 AMP #12 WIRE, SEE | | CIRCUIT #1 ON THE PANEL SCHEDULE. | | | | 5} THE "JACUZZI TUB" MUST BE GFI | | PROTECTED PER 680.71. PLEASE INDICATE | | SAME ON PLANS. | | | | 6} PLEASE VERIFY THE WATER HEATER AT | | 2500 WATTS. SEE LOAD CALC. | | | | 7} THE PENINSULA RECEPTACLE(S) MUST | | COMPLY WITH 210.52(C)(3). | | | | 8} SMOKE DETECTORS ARE REQUIRED PER | | NFPA-72, AND 905.2 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|