Plan Review Notes
Plan Review Notes For Permit 05091299
Permit Number 05091299
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-24 00:00:00********* UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE SOMKE NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED
 AND SOME NEW COMMENTS DUE TO INFORMATION
 ADDED OR CHANGED.
 PLEASE SEE NOTES BELOW WHICH ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO/ YES,PLEASE SEE SOME
 COMMENTS FOR RISER AND PANELS.
  
 **PLEASE PROVIDE MORE INFORMATION
 ON PANELS. TYPE, VOLTAGE, ETC. MCB, MLO
 ETC.215.5
 PLEASE SEE FOLLOWING COMMENTS.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE RISER
 INDICATES PANEL "C" AS 100A'S, HOWEVER
 PANEL "C" IS SHOWN AS 200A'S?
  
 ** PLEASE SHOW AND IDENTIFY ALL
 PANELS, DISCONNECTS ETC ON PLANS.
 COULD NOT LOCATE DISCONNECT SHOWN ON
 RISER FOR PANEL "C" ON PLANS.
 COULD NOT LOCATE POOL PANEL?
 PLEASE SEE NEXT COMMENT.
  
 5)NOTE: NOTE #5 OK.
  
  
 6)NOTE: NOTE #6 NO? PLEASE SEE THE
 PANELS AT MAIN HOUSE SHOULD INDICATE
 MCB'S. (MAIN CIRCUIT BRKRS)
  
 **PLEASE SEE PANELS AT MAIN HOUSE
 SHALL INDICATE MAIN CIRCUIT BREAKER(S)
 (MCB) FOR DISCONNECTING MEANS AT MAIN
 HOUSE.225.31
 THE GROUNDING ELECTRODE ATTACHMENTS FROM
 PREVIOUS NOTE SHALL BE ATTACHED TO THESE
 PANELS.
  
 7)NOTE: NOTE #7, NO, PLEASE SEE THIS IS
 SHOWN AS 400A'S, HOWEVER THE MCB IS NOT
 SHOWN?
  
 **PLEASE SEE 400A METER/MAIN SHALL
 INDICATE 400A MCB. PLEASE SEE ONE 200A
 BRKR IN THIS PANEL IS SHOWN AS MAIN
 BREAKER??
 PLEASE ALSO SEE PANEL "C" IS NOT
 SHOWN/IDENTIFIED ON SCHEDULE FOR
 METER/MAIN.
 215.5
  
 8)NOTE: NOTE #8 OK,HOWEVER,
 PLEASE ALSO KNOW, SD'S ARE NOW SHOWN IN
 MANY LOCATIONS NOT REQUIRED, HOWEVER
 THEY ARE PERMITTED. PLEASE REVISE AT
 THIS TIME, IF OTHER LOCATIONS OTHER THAN
 WHAT IS REQUIRED ARE NOT GOING TO BE
 INSTALLED AS SHOWN? THIS IS ONLY A NOTE;
  
 ** PLEASE SEE PLANS FOR NUMEROUS
 SMOKE DETECTORS MISSING.
 PLEASE SEE NFPA-72 11.5.1.1 WHICH
 REQUIRES SD'S INSIDE AND OUTSIDE ALL
 SLEEPING RMS OR ADAPTABLE SLEEPING
 RMS(THOSE WITH BATHS OR CLOSETS).
 PLEASE SEE SD'S REQUIRED ON ALL LEVELS
 OF A MULTI-LEVEL DWELLING.
 PLEASE SEE SD IN MASTER BEDRM SAHLL BE
 REQUIRED AT FIRST FLR AND SECOND FLR.
 SINCE THIS IS AN OPEN RM, SD FOR FIRST
 FLR SHALL BE WALL MOUNTED IN THE
 VICINITY OF STAIRS LEADING TO FLR ABOVE.
 PLEASE ALSO SEE AREA FOR OTHER STAIRS
 LEADING TO FLR ABOVE. MAIN HOUSE,
 DETACHED CABANA.
 PLEASE SEE SD'S HAVE BEEN REDLINED ON
 PLANS FOR ALL LOCATIONS REQUIRED.
  
 9)NOTE: NOTE #9 NO, PLEASE SEE ALL
 RECEPTS IN GARAGE SHALL BE GFI UNLESS
 FEEDING A DEDICATED CIRCUIT. PLEASE ALSO
 SEE NOTE WITH RESPECT TO THE
 WASHER/DRYER RECEPTS
  
 **PLEASE SEE 210.8A2, WHICH
 REQUIRES ALL RECEPTS IN GARAGE TO BE
 GFI.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE:NOTE #11 NO, PLEASE SEE
 REDLINED PLANS FOR KITCHEN AREA IN MAIN
 HOUSE. PLEASE ALSO SEE NOTE WITH RESPECT
 TO ITEMS ON PLANS WHICH DO NOT SHOW
 RECEPTS.
  
 **PLEASE SEE NUMEROUS GFI RECEPTS
 MISSING ALONG KITCHEN COUNTERSPACES.
 210.8A6, 210.52C1-5
 PLEASE SEE A GFI WILL BE REQUIRED ON 2ND
 FLR "NOOK" AREA OF CABANA ALSO ABOVE
 DISHWASHER.
  
 12)NOTE: NOTE #12, NO/YES, PLEASE SEE
 MOST ALL RECEPTS ADDED, HOWEVER PLEASE
 STILL SEE WALL SPACE NEXT TO FIREPLACE
 AS NOTED ON PERVIOUS REVIEW.
  
 **PLEASE SEE NUMEROUS MISSING
 RECEPTS REQUIRED PER 210.52. 2', 6', 12'
 OF WALL SPACES.
 PLEASE SEE RAIL AREA AT 2ND FLR IS
 CONSIDERED WALL SPACE AND FLR RECEPTS
 WILL BE REQUIRED PER 210.52
 PLEASE CLARIFY AREA T SUNK-IN LIV RM
 NEXT TO FIRE PLACE. ?? WALL SPACE??
 PLEASE SEE MANY OF THE ABOVE HAVE BEEN
 REDLINED ON PLANS WHERE REQUIRED. MANY
 OF MISSING.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK.
  
  
 16)NOTE: NOTE #16 OK.P
  
 17)NOTE: NOTE #17 OK.
  
  
 18)NOTE: NOTE #18 OK.
  
 19)NOTE: NOTE #19 NO, PLEASE SEE PANEL
 SCHEDULE STILL DOES NOT LOST THIS
 DEDICATED CIRCUIT??
  
 ** PLEASE SEE SYMBOL FOR JACUZZI
 TUB/WHIRLPOOL TUB IS BEING SHOWN AS
 220V, HOWEVER THIS IS NOT LOCATED ON
 PANEL SCHEDULE(S) OR LOAD CALCS??
 PLEASE SEE 680.71, FOR REQUIRED GFI
 PROTECTION.
 PLEASE ALSO ADJUST LOAD CALCS.
  
 20)NOTE: NOTE #20, NO/YES, PLEASE SEE
 THESE CIRCUITS WERE MOVED TO THE
 DETACHED BLDG PANEL "C" HOWEVER , PLEASE
 SEE LOAD SHOWN INDCIATES 2400VA ON A
 1-POLE 20A CIRCUIT?? PLEASE KNOW, THIS
 WELL EXCEEDS RATING OF THIS CIRCUIT,
 PELASE VERIFY LOAD/HP RATING OF THESE
 MOTORS AS 2400VA IS NOT TYPICAL?
 PLEASE KNOW, MAX VA ON A 20A CIRCUIT IS
 1920VA.
  
 ** PLEASE SEE A GDO IS SHOWN ON
 LOAD CALCS FOR PANELS LOCATED ON MAIN
 HOUSE,HOWEVER NO GDO COULD BE LOCATED AT
 MAIN HOUSE?
 PLEASE SEE DETACHED "GARAGE" DOES NOT
 INDICATE OR SHOW A GARAGE DOOR OR GDO.
 PLEASE INCLUDE IN PANEL "C" , LOADS ETC.
 215.5
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 OK. SEE BELOW.
  
 23)NOTE: NOTE #23 OK.
  
  
 24)NOTE: NOTE #24 NO, PLEASE SEE NOW
 THAT LOADS AND OCP HAS BEEN REVISED,
 PLEASE SEE 60A OCP ON #8 AWG.
 PLEASE ADJUST REDLINED PLANS,
 240.4,310.16
  
  
 **PLEASE SEE PREVIOUS NOTE, ONCE
 A/C UNITS HAVE BEEN CORRELATED, PLEASE
 SEE 424.3B FOR MIN OCP OF 125% OF HEAT
 KW LOAD. PLEASE ALSO NOTE, MAX OCP OF
 150%
 PLEASE ADJUST OCP AND CONDUCTORS AS
 LISTED ON PLANS.
 PLEASE SEE LOAD CALCS AND KW RATING
 SHOWN.
  
 25)NOTE: NOTE #25, NO, PLEASE SEE PLANS
 STILL MISSING POOL PANEL SCHEDULE/LOADS.
  
 ** PLEASE PROVIDE LOADS ON EACH
 PANEL.PLEASE SEE MISSING POOL PANEL,
 PANEL SCHEDULE. LOADS ARE SHOWN ON MAIN
 CALCS, HOWEVER THESE LOADS CAN NOT BE
 VERIFIED.
 PLEASE KNOW, ALL CONTINUOUS LOADS SHALL
 BE SHOWN AT 125%. (3 OR MORE HRS).
 POOL PUMP, HEAT PUMPS?
 215.3,230.42 ETC.
  
 26)NOTE: NOTE #26 OK
  
 27)NOTE:NOTE #27, NO, PLEASE SEE MANY
 ITEMS ON PLANS WHICH DO NOT CORRELATE
 WIHT PANELS, ETC. PLEASE SEE DISP, WINE
 FRIG, TRASH COMP ETC WHICH ARE ON PLANS,
 WITH OUT ANY ELECTRICAL DEVICES TO FEED
 THESE APPLIANCES??
 PLEASE ALSO SEE PLANS INDICATE TWO
 DISHWASHERS, ONLY ONE ONPANEL
 SCHEDULE? AND NO DEVICES ON PLANS?
 PLEASE KNOW, AS FOR LOADS OF DEDICATED
 CIRCUITS, NO MORE THAN 750VA OF
 MOTOR/FRIG LOADS ARE PERMITTED ON OTHER
 SMALL APPL CIRCUITS.
  
 **PLEASE CORRELATE ALL DEDICATED
 CIRCUITS WHICH ARE SHOWN ON PLANS,
 HOWEVER NOT ALL ARE LISTED ON PANEL
 SCHEDULES.
 COULD NOT LOCATE ELEC OVEN ON PLANS?
 PLEASE MOVE ANY 220V OUTLETS FOR
 OVENS/RANGES DIRECTLY BEHIND UNITS.
 PLEASE SEE PLANS SHOW TWO RANGES, HOWEVR
 PANEL SCHEDULE ONLY SHOWS ONE??
 PLEASE SEE ZONING NOTES.
 PLEASE SEE # OF ICE MAKERS LISTED ON
 LOAD CALCS, YET ONLY ONE DEDICATED
 CIRCUIT IS SHOWN ON PANEL SCHEDULE?
 PLEASE CORRELATE OTHERS.
  
 28)NOTE: NOTE #28 OK, 220V RECEPT
 REMOVED. PLEASE BE AWARE OF USE OF THE
 120A RECEPT SHOWN NEXT TO FRIG.
  
 29)NOTE: NOTE #29OK.
  
  
 30)NOTE: NOTE #30 OK/NO, PLEASE SEE PAT
 OF THIS NOTE DONE, PLEASE SEE MAIN HOSUE
 WHICH STILL SHOWS A MICRO ON PANEL
 SCHEDULE, BUT NO ON PLANS/
  
 **PLEASE SEE DISHWASHER IS SHOWN
 ON PLANS FOR CABANA, HOWEVER PANEL
 SCHEDULE AND LOAD CALCS DO NOT INDICATE
 THE SAME.??
 PLEASE ALSO SEE MICROWAVE SHOWN ON PANEL
 SCHEDULE, BUT NOT ON PLANS FOR DEDICATED
 CIRCUIT??
  
 31)NOTE: NOTE #31 PLEASE SEE AREA OF W/D
 AT DETACHED GARAGE, WHICH SEEMS TO
 INDICATE A DEDICATED RECEPT FOR A
 WASHER? HOWEVER PANEL SCHEDULE MENTIONS
 DRYER ONLY AND PLANS SHOWS WHAT APPEARS
 TO BE A STACKABLE UNIT??
 PLEASE KNOW, IF THERE IS A WASHER, THEN
 THIS WOULD NOT BE A GFI FOR A DEDICATED
 CIRCUIT.
 PLEASE ALSO SEE THIS IN MAIN HOUSE
 LANUDRY RM.
 PLEASE ADJUST PANEL SCHEDULE AND ANY
 LOADS ACCORDINGLY IF NEEDED.
  
 ** PLEASE SEE GFI SHOWN ON
 COUNTERSPACE IN DETACHED CABANA, IS
 SHOWN AS "WP" ?? THIS IS PERMITTED,
 HOWEVER NOT REQUIRED.
 210.8A6
  
 32)NOTE: NOTE #32 OK. THESE WERE REMOVED
  
  
 ************************
  
 ADDITIONAL NEW NOTES,
  
 33)NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO PLANS REVIEWS AND REPEAT
 COMMENTS. PLEASE KNOW THIS IS ONLY
 NOTICE GIVEN AT THIS TIME.
  
 34)NOTE: PLEASE SEE RISER WHICH IS
 MISSING THE SIZE OF THE FEEDERS TO SUB
 PANELS "C" AND "POOL PANEL". PLEASE SEE
 RISER SHOWS 3#(?) THIS IS BLANK?
 240.4,310.16,215.5
 PLEASE KNOW, MANY OF THE ABOVE ITEMS
 HAVE BEEN REDLINED ON PLANS AT LOCATIONS
 OF NOTES.
  
 35)NOTE: PLEASE SEE SOME NEW NOTES WERE
 PART OF THE NOTES ABOVE 1-32
  
 ** PLEASE SEE ONE SET OF PLANS ARE
 REDLINED FOR MOST OF THE ABOVE COMMENTS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE SET OF
 OLD/VOIDED SHEETSREQUIRED FOR
 REFERENCE.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REIVEW
 561-805-6717
 [email protected]
  
  
  
  
  
  