2006-02-24 00:00:00 | ********* UNSAT 2ND REVIEW ********** |
| |
| ** PLEASE SEE SOMKE NOTES FROM PREVIOUS |
| REVIEW WHICH STILL NEED TO BE ADDRESSED |
| AND SOME NEW COMMENTS DUE TO INFORMATION |
| ADDED OR CHANGED. |
| PLEASE SEE NOTES BELOW WHICH ARE TAKEN |
| DIRECTLY FROM PREVIOUS REVIEW. |
| |
| |
| 1)NOTE: NOTE #1 OK. |
| |
| 2)NOTE: NOTE #2 OK. |
| |
| 3)NOTE: NOTE #3 NO/ YES,PLEASE SEE SOME |
| COMMENTS FOR RISER AND PANELS. |
| |
| **PLEASE PROVIDE MORE INFORMATION |
| ON PANELS. TYPE, VOLTAGE, ETC. MCB, MLO |
| ETC.215.5 |
| PLEASE SEE FOLLOWING COMMENTS. |
| |
| 4)NOTE: NOTE #4 NO, PLEASE SEE RISER |
| INDICATES PANEL "C" AS 100A'S, HOWEVER |
| PANEL "C" IS SHOWN AS 200A'S? |
| |
| ** PLEASE SHOW AND IDENTIFY ALL |
| PANELS, DISCONNECTS ETC ON PLANS. |
| COULD NOT LOCATE DISCONNECT SHOWN ON |
| RISER FOR PANEL "C" ON PLANS. |
| COULD NOT LOCATE POOL PANEL? |
| PLEASE SEE NEXT COMMENT. |
| |
| 5)NOTE: NOTE #5 OK. |
| |
| |
| 6)NOTE: NOTE #6 NO? PLEASE SEE THE |
| PANELS AT MAIN HOUSE SHOULD INDICATE |
| MCB'S. (MAIN CIRCUIT BRKRS) |
| |
| **PLEASE SEE PANELS AT MAIN HOUSE |
| SHALL INDICATE MAIN CIRCUIT BREAKER(S) |
| (MCB) FOR DISCONNECTING MEANS AT MAIN |
| HOUSE.225.31 |
| THE GROUNDING ELECTRODE ATTACHMENTS FROM |
| PREVIOUS NOTE SHALL BE ATTACHED TO THESE |
| PANELS. |
| |
| 7)NOTE: NOTE #7, NO, PLEASE SEE THIS IS |
| SHOWN AS 400A'S, HOWEVER THE MCB IS NOT |
| SHOWN? |
| |
| **PLEASE SEE 400A METER/MAIN SHALL |
| INDICATE 400A MCB. PLEASE SEE ONE 200A |
| BRKR IN THIS PANEL IS SHOWN AS MAIN |
| BREAKER?? |
| PLEASE ALSO SEE PANEL "C" IS NOT |
| SHOWN/IDENTIFIED ON SCHEDULE FOR |
| METER/MAIN. |
| 215.5 |
| |
| 8)NOTE: NOTE #8 OK,HOWEVER, |
| PLEASE ALSO KNOW, SD'S ARE NOW SHOWN IN |
| MANY LOCATIONS NOT REQUIRED, HOWEVER |
| THEY ARE PERMITTED. PLEASE REVISE AT |
| THIS TIME, IF OTHER LOCATIONS OTHER THAN |
| WHAT IS REQUIRED ARE NOT GOING TO BE |
| INSTALLED AS SHOWN? THIS IS ONLY A NOTE; |
| |
| ** PLEASE SEE PLANS FOR NUMEROUS |
| SMOKE DETECTORS MISSING. |
| PLEASE SEE NFPA-72 11.5.1.1 WHICH |
| REQUIRES SD'S INSIDE AND OUTSIDE ALL |
| SLEEPING RMS OR ADAPTABLE SLEEPING |
| RMS(THOSE WITH BATHS OR CLOSETS). |
| PLEASE SEE SD'S REQUIRED ON ALL LEVELS |
| OF A MULTI-LEVEL DWELLING. |
| PLEASE SEE SD IN MASTER BEDRM SAHLL BE |
| REQUIRED AT FIRST FLR AND SECOND FLR. |
| SINCE THIS IS AN OPEN RM, SD FOR FIRST |
| FLR SHALL BE WALL MOUNTED IN THE |
| VICINITY OF STAIRS LEADING TO FLR ABOVE. |
| PLEASE ALSO SEE AREA FOR OTHER STAIRS |
| LEADING TO FLR ABOVE. MAIN HOUSE, |
| DETACHED CABANA. |
| PLEASE SEE SD'S HAVE BEEN REDLINED ON |
| PLANS FOR ALL LOCATIONS REQUIRED. |
| |
| 9)NOTE: NOTE #9 NO, PLEASE SEE ALL |
| RECEPTS IN GARAGE SHALL BE GFI UNLESS |
| FEEDING A DEDICATED CIRCUIT. PLEASE ALSO |
| SEE NOTE WITH RESPECT TO THE |
| WASHER/DRYER RECEPTS |
| |
| **PLEASE SEE 210.8A2, WHICH |
| REQUIRES ALL RECEPTS IN GARAGE TO BE |
| GFI. |
| |
| 10)NOTE: NOTE #10 OK. |
| |
| 11)NOTE:NOTE #11 NO, PLEASE SEE |
| REDLINED PLANS FOR KITCHEN AREA IN MAIN |
| HOUSE. PLEASE ALSO SEE NOTE WITH RESPECT |
| TO ITEMS ON PLANS WHICH DO NOT SHOW |
| RECEPTS. |
| |
| **PLEASE SEE NUMEROUS GFI RECEPTS |
| MISSING ALONG KITCHEN COUNTERSPACES. |
| 210.8A6, 210.52C1-5 |
| PLEASE SEE A GFI WILL BE REQUIRED ON 2ND |
| FLR "NOOK" AREA OF CABANA ALSO ABOVE |
| DISHWASHER. |
| |
| 12)NOTE: NOTE #12, NO/YES, PLEASE SEE |
| MOST ALL RECEPTS ADDED, HOWEVER PLEASE |
| STILL SEE WALL SPACE NEXT TO FIREPLACE |
| AS NOTED ON PERVIOUS REVIEW. |
| |
| **PLEASE SEE NUMEROUS MISSING |
| RECEPTS REQUIRED PER 210.52. 2', 6', 12' |
| OF WALL SPACES. |
| PLEASE SEE RAIL AREA AT 2ND FLR IS |
| CONSIDERED WALL SPACE AND FLR RECEPTS |
| WILL BE REQUIRED PER 210.52 |
| PLEASE CLARIFY AREA T SUNK-IN LIV RM |
| NEXT TO FIRE PLACE. ?? WALL SPACE?? |
| PLEASE SEE MANY OF THE ABOVE HAVE BEEN |
| REDLINED ON PLANS WHERE REQUIRED. MANY |
| OF MISSING. |
| |
| 13)NOTE: NOTE #13 OK. |
| |
| 14)NOTE: NOTE #14 OK. |
| |
| 15)NOTE: NOTE #15 OK. |
| |
| |
| 16)NOTE: NOTE #16 OK.P |
| |
| 17)NOTE: NOTE #17 OK. |
| |
| |
| 18)NOTE: NOTE #18 OK. |
| |
| 19)NOTE: NOTE #19 NO, PLEASE SEE PANEL |
| SCHEDULE STILL DOES NOT LOST THIS |
| DEDICATED CIRCUIT?? |
| |
| ** PLEASE SEE SYMBOL FOR JACUZZI |
| TUB/WHIRLPOOL TUB IS BEING SHOWN AS |
| 220V, HOWEVER THIS IS NOT LOCATED ON |
| PANEL SCHEDULE(S) OR LOAD CALCS?? |
| PLEASE SEE 680.71, FOR REQUIRED GFI |
| PROTECTION. |
| PLEASE ALSO ADJUST LOAD CALCS. |
| |
| 20)NOTE: NOTE #20, NO/YES, PLEASE SEE |
| THESE CIRCUITS WERE MOVED TO THE |
| DETACHED BLDG PANEL "C" HOWEVER , PLEASE |
| SEE LOAD SHOWN INDCIATES 2400VA ON A |
| 1-POLE 20A CIRCUIT?? PLEASE KNOW, THIS |
| WELL EXCEEDS RATING OF THIS CIRCUIT, |
| PELASE VERIFY LOAD/HP RATING OF THESE |
| MOTORS AS 2400VA IS NOT TYPICAL? |
| PLEASE KNOW, MAX VA ON A 20A CIRCUIT IS |
| 1920VA. |
| |
| ** PLEASE SEE A GDO IS SHOWN ON |
| LOAD CALCS FOR PANELS LOCATED ON MAIN |
| HOUSE,HOWEVER NO GDO COULD BE LOCATED AT |
| MAIN HOUSE? |
| PLEASE SEE DETACHED "GARAGE" DOES NOT |
| INDICATE OR SHOW A GARAGE DOOR OR GDO. |
| PLEASE INCLUDE IN PANEL "C" , LOADS ETC. |
| 215.5 |
| |
| 21)NOTE: NOTE #21 OK. |
| |
| 22)NOTE: NOTE #22 OK. SEE BELOW. |
| |
| 23)NOTE: NOTE #23 OK. |
| |
| |
| 24)NOTE: NOTE #24 NO, PLEASE SEE NOW |
| THAT LOADS AND OCP HAS BEEN REVISED, |
| PLEASE SEE 60A OCP ON #8 AWG. |
| PLEASE ADJUST REDLINED PLANS, |
| 240.4,310.16 |
| |
| |
| **PLEASE SEE PREVIOUS NOTE, ONCE |
| A/C UNITS HAVE BEEN CORRELATED, PLEASE |
| SEE 424.3B FOR MIN OCP OF 125% OF HEAT |
| KW LOAD. PLEASE ALSO NOTE, MAX OCP OF |
| 150% |
| PLEASE ADJUST OCP AND CONDUCTORS AS |
| LISTED ON PLANS. |
| PLEASE SEE LOAD CALCS AND KW RATING |
| SHOWN. |
| |
| 25)NOTE: NOTE #25, NO, PLEASE SEE PLANS |
| STILL MISSING POOL PANEL SCHEDULE/LOADS. |
| |
| ** PLEASE PROVIDE LOADS ON EACH |
| PANEL.PLEASE SEE MISSING POOL PANEL, |
| PANEL SCHEDULE. LOADS ARE SHOWN ON MAIN |
| CALCS, HOWEVER THESE LOADS CAN NOT BE |
| VERIFIED. |
| PLEASE KNOW, ALL CONTINUOUS LOADS SHALL |
| BE SHOWN AT 125%. (3 OR MORE HRS). |
| POOL PUMP, HEAT PUMPS? |
| 215.3,230.42 ETC. |
| |
| 26)NOTE: NOTE #26 OK |
| |
| 27)NOTE:NOTE #27, NO, PLEASE SEE MANY |
| ITEMS ON PLANS WHICH DO NOT CORRELATE |
| WIHT PANELS, ETC. PLEASE SEE DISP, WINE |
| FRIG, TRASH COMP ETC WHICH ARE ON PLANS, |
| WITH OUT ANY ELECTRICAL DEVICES TO FEED |
| THESE APPLIANCES?? |
| PLEASE ALSO SEE PLANS INDICATE TWO |
| DISHWASHERS, ONLY ONE ONPANEL |
| SCHEDULE? AND NO DEVICES ON PLANS? |
| PLEASE KNOW, AS FOR LOADS OF DEDICATED |
| CIRCUITS, NO MORE THAN 750VA OF |
| MOTOR/FRIG LOADS ARE PERMITTED ON OTHER |
| SMALL APPL CIRCUITS. |
| |
| **PLEASE CORRELATE ALL DEDICATED |
| CIRCUITS WHICH ARE SHOWN ON PLANS, |
| HOWEVER NOT ALL ARE LISTED ON PANEL |
| SCHEDULES. |
| COULD NOT LOCATE ELEC OVEN ON PLANS? |
| PLEASE MOVE ANY 220V OUTLETS FOR |
| OVENS/RANGES DIRECTLY BEHIND UNITS. |
| PLEASE SEE PLANS SHOW TWO RANGES, HOWEVR |
| PANEL SCHEDULE ONLY SHOWS ONE?? |
| PLEASE SEE ZONING NOTES. |
| PLEASE SEE # OF ICE MAKERS LISTED ON |
| LOAD CALCS, YET ONLY ONE DEDICATED |
| CIRCUIT IS SHOWN ON PANEL SCHEDULE? |
| PLEASE CORRELATE OTHERS. |
| |
| 28)NOTE: NOTE #28 OK, 220V RECEPT |
| REMOVED. PLEASE BE AWARE OF USE OF THE |
| 120A RECEPT SHOWN NEXT TO FRIG. |
| |
| 29)NOTE: NOTE #29OK. |
| |
| |
| 30)NOTE: NOTE #30 OK/NO, PLEASE SEE PAT |
| OF THIS NOTE DONE, PLEASE SEE MAIN HOSUE |
| WHICH STILL SHOWS A MICRO ON PANEL |
| SCHEDULE, BUT NO ON PLANS/ |
| |
| **PLEASE SEE DISHWASHER IS SHOWN |
| ON PLANS FOR CABANA, HOWEVER PANEL |
| SCHEDULE AND LOAD CALCS DO NOT INDICATE |
| THE SAME.?? |
| PLEASE ALSO SEE MICROWAVE SHOWN ON PANEL |
| SCHEDULE, BUT NOT ON PLANS FOR DEDICATED |
| CIRCUIT?? |
| |
| 31)NOTE: NOTE #31 PLEASE SEE AREA OF W/D |
| AT DETACHED GARAGE, WHICH SEEMS TO |
| INDICATE A DEDICATED RECEPT FOR A |
| WASHER? HOWEVER PANEL SCHEDULE MENTIONS |
| DRYER ONLY AND PLANS SHOWS WHAT APPEARS |
| TO BE A STACKABLE UNIT?? |
| PLEASE KNOW, IF THERE IS A WASHER, THEN |
| THIS WOULD NOT BE A GFI FOR A DEDICATED |
| CIRCUIT. |
| PLEASE ALSO SEE THIS IN MAIN HOUSE |
| LANUDRY RM. |
| PLEASE ADJUST PANEL SCHEDULE AND ANY |
| LOADS ACCORDINGLY IF NEEDED. |
| |
| ** PLEASE SEE GFI SHOWN ON |
| COUNTERSPACE IN DETACHED CABANA, IS |
| SHOWN AS "WP" ?? THIS IS PERMITTED, |
| HOWEVER NOT REQUIRED. |
| 210.8A6 |
| |
| 32)NOTE: NOTE #32 OK. THESE WERE REMOVED |
| |
| |
| ************************ |
| |
| ADDITIONAL NEW NOTES, |
| |
| 33)NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| RESPECT TO PLANS REVIEWS AND REPEAT |
| COMMENTS. PLEASE KNOW THIS IS ONLY |
| NOTICE GIVEN AT THIS TIME. |
| |
| 34)NOTE: PLEASE SEE RISER WHICH IS |
| MISSING THE SIZE OF THE FEEDERS TO SUB |
| PANELS "C" AND "POOL PANEL". PLEASE SEE |
| RISER SHOWS 3#(?) THIS IS BLANK? |
| 240.4,310.16,215.5 |
| PLEASE KNOW, MANY OF THE ABOVE ITEMS |
| HAVE BEEN REDLINED ON PLANS AT LOCATIONS |
| OF NOTES. |
| |
| 35)NOTE: PLEASE SEE SOME NEW NOTES WERE |
| PART OF THE NOTES ABOVE 1-32 |
| |
| ** PLEASE SEE ONE SET OF PLANS ARE |
| REDLINED FOR MOST OF THE ABOVE COMMENTS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM |
| SETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. PLEASE ONLY SUBMIT ONE SET OF |
| OLD/VOIDED SHEETSREQUIRED FOR |
| REFERENCE. |
| |
| PLEASE SEE ANY COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS , |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |