Plan Review Notes
Plan Review Notes For Permit 05091299
Permit Number 05091299
Review Stop M
Sequence Number 1
Notes
Date Text
2005-10-12 00:00:00*** DENIED ***
 1) EQUIP. INFO. FOR A/C SYSTEM RHEEM
 COND. RMAB-048J IS MISSING ON PLANS.
 2) NEED MANUFACTURE'S SPEC. SHEETS FOR
 GAS FIREPLACE.
 3) NEED COMBUSTION AIR CALCULATIONS FOR
 GAS FIREPLACE.
 4) SUPPLY AIR DUCT ON 2ND. FLOOR MAIN
 HOUSE, FROM AHU TO 1ST. FLOOR IS NOT
 SIZED.
 5) PROVIED AUXILIARY DRAIN PANSWITH
 DRAIN PROTECTION UNDER AHU'S PER 2001
 FBC/M 307.2.3 .
 6) DRAIN LINES FOR AHU'S NOT SHOWING ON
 PLANS PER 2001 FBC/M 307.2 .
 7) DRYER TO BE VENTED PER 2001 FBC/M 504
 .
 8) PLEASE SEE ELECTRICAL REVIEW
 REGUARDING A/C SYSTEMS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.