Plan Review Notes
Plan Review Notes For Permit 05091299
Permit Number 05091299
Review Stop E
Sequence Number 1
Notes
Date Text
2005-10-06 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS FOR ADJUSTED VALUE FOR SCOPE OF
 WORK.
 104.6.5, FBC, CITY-WIDE ADMINISTRATIVE
 CODE.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATING FOR MAIN WAS SUBMITTED,
 HOWEVER PLEASE INDICATE PANELS ALSO.
 PLEASE SEE FOLLWING COMMENT.
  
 3)NOTE: PLEASE PROVIDE MORE INFORMATION
 ON PANELS. TYPE, VOLTAGE, ETC. MCB, MLO
 ETC.215.5
 PLEASE SEE FOLLOWING COMMENTS.
  
 4)NOTE: PLEASE SHOW AND IDENTIFY ALL
 PANELS, DISCONNECTS ETC ON PLANS.
 COULD NOT LOCATE DISCONNECT SHOWN ON
 RISER FOR PANEL "C" ON PLANS.
 COULD NOT LOCATE POOL PANEL?
 PLEASE SEE NEXT COMMENT.
  
 5)NOTE: PLEASE SEE PLANS WHICH INDICATE
 METER/MAIN AT DETACHED BLDG, HOWEVER
 PANEL "C" SEEMS TO BE SHOWN WITH THE
 GROUNDING ELECTRODE SYSTEM WHICH IS
 ACTUALLY REQUIRED FOR PANELS "A" AND "B"
 AT MAIN HOUSE.
 250.32
  
 6)NOTE: PLEASE SEE PANELS AT MAIN HOUSE
 SHALL INDICATE MAIN CIRCUIT BREAKER(S)
 (MCB) FOR DISCONNECTING MEANS AT MAIN
 HOUSE.225.31
 THE GROUNDING ELECTRODE ATTACHMENTS FROM
 PREVIOUS NOTE SHALL BE ATTACHED TO THESE
 PANELS.
  
 7)NOTE: PLEASE SEE 400A METER/MAIN SHALL
 INDICATE 400A MCB. PLEASE SEE ONE 200A
 BRKR IN THIS PANEL IS SHOWN AS MAIN
 BREAKER??
 PLEASE ALSO SEE PANEL "C" IS NOT
 SHOWN/IDENTIFIED ON SCHEDULE FOR
 METER/MAIN.
 215.5
  
 8)NOTE: PLEASE SEE PLANS FOR NUMEROUS
 SMOKE DETECTORS MISSING.
 PLEASE SEE NFPA-72 11.5.1.1 WHICH
 REQUIRES SD'S INSIDE AND OUTSIDE ALL
 SLEEPING RMS OR ADAPTABLE SLEEPING
 RMS(THOSE WITH BATHS OR CLOSETS).
 PLEASE SEE SD'S REQUIRED ON ALL LEVELS
 OF A MULTI-LEVEL DWELLING.
 PLEASE SEE SD IN MASTER BEDRM SAHLL BE
 REQUIRED AT FIRST FLR AND SECOND FLR.
 SINCE THIS IS AN OPEN RM, SD FOR FIRST
 FLR SHALL BE WALL MOUNTED IN THE
 VICINITY OF STAIRS LEADING TO FLR ABOVE.
 PLEASE ALSO SEE AREA FOR OTHER STAIRS
 LEADING TO FLR ABOVE. MAIN HOUSE,
 DETACHED CABANA.
 PLEASE SEE SD'S HAVE BEEN REDLINED ON
 PLANS FOR ALL LOCATIONS REQUIRED.
  
 9)NOTE: PLEASE SEE 210.8A2, WHICH
 REQUIRES ALL RECEPTS IN GARAGE TO BE
 GFI.
  
 10)NOTE: PLEASE SEE MISSING GFI RECEPTS
 FOR A/C EQUIPMENT.
 210.8A, 210.63
  
 11)NOTE: PLEASE SEE NUMEROUS GFI RECEPTS
 MISSING ALONG KITCHEN COUNTERSPACES.
 210.8A6, 210.52C1-5
 PLEASE SEE A GFI WILL BE REQUIRED ON 2ND
 FLR "NOOK" AREA OF CABANA ALSO ABOVE
 DISHWASHER.
  
 12)NOTE: PLEASE SEE NUMEROUS MISSING
 RECEPTS REQUIRED PER 210.52. 2', 6', 12'
 OF WALL SPACES.
 PLEASE SEE RAIL AREA AT 2ND FLR IS
 CONSIDERED WALL SPACE AND FLR RECEPTS
 WILL BE REQUIRED PER 210.52
 PLEASE CLARIFY AREA T SUNK-IN LIV RM
 NEXT TO FIRE PLACE. ?? WALL SPACE??
 PLEASE SEE MANY OF THE ABOVE HAVE BEEN
 REDLINED ON PLANS WHERE REQUIRED. MANY
 OF MISSING.
  
 13)NOTE: PLEASE SEE MISSING HALLWAY
 RECEPTS PER 210.52H
 REDLINED.
  
 14)NOTE: PLEASE SEE MISSING GFI RECEPTS
 PER 210.52D,210.11C3,210.8
  
 15)NOTE: PLEASE SEE ALL RECEPTS WITIN 6'
 OF SINKS SHALL BE GFI/GFI PROTECTED.
 (LAUNDRY RM )210.8A
  
 16)NOTE:PLEASE SEE MISSING EGRESS
 LIGHTING CONTROL AT LOCATION OF MASTER
 BEDRM, HALL/LIVING RM ETC.
 210.70
 PLEASE CORRELATE SWITCHES SHOWN FOR
 MASTER BEDRM LTS, SCONCES ETC.
 STAIR-WAY LT CONTROL. GRADE LEVEL
 ACCESS. MOST HAVE BEEN REDLINED ON PLANS
 AT LOCATIONS MENTIONED.
 LS 101 7.8
  
 17)NOTE: PLEASE LIST THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER
 210.52D,210.11C3. PLEASE SEE THESE ARE
 REQUIRED TO BE 20A AND #12 AWG.
  
 18)NOTE: PLEASE SEE NO SWITCHES SHALL BE
 LOCATED WITHIN THE 3' ZONE OF A
 TUB/JACUZZI TUB. PLEASE SEE NO RECEPTS
 SHALL BE LOCATED WITH 3' OF TUB.
 PLEASE SEE REDLINED PLANS FOR MASTER
 BATH RM LT CONTROLS, BEDRM #3.
 680.71, 410.4
  
 19)NOTE: PLEASE SEE SYMBOL FOR JACUZZI
 TUB/WHIRLPOOL TUB IS BEING SHOWN AS
 220V, HOWEVER THIS IS NOT LOCATED ON
 PANEL SCHEDULE(S) OR LOAD CALCS??
 PLEASE SEE 680.71, FOR REQUIRED GFI
 PROTECTION.
 PLEASE ALSO ADJUST LOAD CALCS.
  
 20)NOTE: PLEASE SEE A GDO IS SHOWN ON
 LOAD CALCS FOR PANELS LOCATED ON MAIN
 HOUSE,HOWEVER NO GDO COULD BE LOCATED AT
 MAIN HOUSE?
 PLEASE SEE DETACHED "GARAGE" DOES NOT
 INDICATE OR SHOW A GARAGE DOOR OR GDO.
 PLEASE INCLUDE IN PANEL "C" , LOADS ETC.
 215.5
  
 21)NOTE: PLEASE SEE MISSING DISCONNECTS
 REQUIRED FOR WATER HEATERS.
 422.31
  
 22)NOTE: PLEASE SEE MISSING
 DISCONNECTING MEANS REQUIRED FOR AHU'S ,
 PER 440.11
 PLEASE SEE MIN CLEARENCES REQUIRED PER
 110.26.
 PLEASE ALSO SEE DISCONNECT CLEARENCE
 REQUIRED FOR CU'S OUTSIDE.
 PLEAS ADJUST.
  
 23)NOTE: PLEASE CORRELATE ALL A/C LOADS
 ON LOAD CALCS, NUMBER OF UNITS INDICATED
 ON PANEL SCHEDULE(S) AND NUMBER OF UNITS
 SHOWN ON PLANS.
 PLEASE SEE LOAD CALCS FOR MAIN HOUSE
 INDICATE 4-5 AHU'S??? WHEREAS PLANS SHOW
 3-CU'S AND PANEL SCHEDULES ONLY INDICATE
 2 UNITS TOTAL???
 215.5 ETC.
  
 24)NOTE: PLEASE SEE PREVIOUS NOTE, ONCE
 A/C UNITS HAVE BEEN CORRELATED, PLEASE
 SEE 424.3B FOR MIN OCP OF 125% OF HEAT
 KW LOAD. PLEASE ALSO NOTE, MAX OCP OF
 150%
 PLEASE ADJUST OCP AND CONDUCTORS AS
 LISTED ON PLANS.
 PLEASE SEE LOAD CALCS AND KW RATING
 SHOWN.
  
 25)NOTE: PLEASE PROVIDE LOADS ON EACH
 PANEL.PLEASE SEE MISSING POOL PANEL,
 PANEL SCHEDULE. LOADS ARE SHOWN ON MAIN
 CALCS, HOWEVER THESE LOADS CAN NOT BE
 VERIFIED.
 PLEASE KNOW, ALL CONTINUOUS LOADS SHALL
 BE SHOWN AT 125%. (3 OR MORE HRS).
 POOL PUMP, HEAT PUMPS?
 215.3,230.42 ETC.
  
 26)NOTE: PLEASE SEE 250.66, 310.15B6 FOR
 MIN GROUNDING ELECTRODE CONDUCTOR.
 PLEASE SEE 1/0 MIN AT MAIN SERVICE AT
 DETACHED GARAGE. PLEASE ALSO SEE MIN AT
 MAIN HOUSE SHALL BE #2
  
 27)NOTE: PLEASE CORRELATE ALL DEDICATED
 CIRCUITS WHICH ARE SHOWN ON PLANS,
 HOWEVER NOT ALL ARE LISTED ON PANEL
 SCHEDULES.
 COULD NOT LOCATE ELEC OVEN ON PLANS?
 PLEASE MOVE ANY 220V OUTLETS FOR
 OVENS/RANGES DIRECTLY BEHIND UNITS.
 PLEASE SEE PLANS SHOW TWO RANGES, HOWEVR
 PANEL SCHEDULE ONLY SHOWS ONE??
 PLEASE SEE ZONING NOTES.
 PLEASE SEE # OF ICE MAKERS LISTED ON
 LOAD CALCS, YET ONLY ONE DEDICATED
 CIRCUIT IS SHOWN ON PANEL SCHEDULE?
 PLEASE CORRELATE OTHERS.
  
 28)NOTE: PLEASE VERIFY WHAT APPEARS TO
 BE A 220V RECEPT SHOWN IN PANTRY.??
 PLEASE ALSO CALRIFY RECEPTS SHOWN IN
 CLOSETS? ABOVE? BELOW? COMBUSTIBLES.?
 PLEASE BE AWARE OF INTENDED USE OF THESE
 WHICH MAY NOT PERMIT THESE TO BE LOCATED
 IN CLOSETS.
 240.24 ETC
  
 29)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 30)NOTE: PLEASE SEE DISHWASHER IS SHOWN
 ON PLANS FOR CABANA, HOWEVER PANEL
 SCHEDULE AND LOAD CALCS DO NOT INDICATE
 THE SAME.??
 PLEASE ALSO SEE MICROWAVE SHOWN ON PANEL
 SCHEDULE, BUT NOT ON PLANS FOR DEDICATED
 CIRCUIT??
  
 31)NOTE: PLEASE SEE GFI SHOWN ON
 COUNTERSPACE IN DETACHED CABANA, IS
 SHOWN AS "WP" ?? THIS IS PERMITTED,
 HOWEVER NOT REQUIRED.
 210.8A6
  
 32)NOTE: PLEASE IDENTIFY OTHER 220V
 RECEPTS SHOWN ON PLANS , HOWEVER THESE
 ARE NO LISTED IN LOAD CALCS OR ON PANEL
 SCHEDULES??
 PLEASE SEE CABANA AND MAIN HOUSE.
  
  
 PLEASE CORRELATE ALL A/C EQUIPMENT WITH
 MECHANICAL PLANS.
 THESE DO NOT MATCH.
  
 PLEASE KNOW, MANY OF THE ABOVE ITEMS
 HAVE BEEN REDLINED ON PLANS AT LOCATIONS
 OF NOTES.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE SET OF
 OLD/VOIDED SHEETSREQUIRED FOR
 REFERENCE.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REIVEW
 561-805-6717
 [email protected]
  
  
  
  
  
  