2005-10-06 00:00:00 | ********* UNSAT ********** |
| |
| 1)NOTE: PLEASE SEE BUILDING REVIEW |
| COMMENTS FOR ADJUSTED VALUE FOR SCOPE OF |
| WORK. |
| 104.6.5, FBC, CITY-WIDE ADMINISTRATIVE |
| CODE. |
| |
| 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| AIC RATING FOR MAIN WAS SUBMITTED, |
| HOWEVER PLEASE INDICATE PANELS ALSO. |
| PLEASE SEE FOLLWING COMMENT. |
| |
| 3)NOTE: PLEASE PROVIDE MORE INFORMATION |
| ON PANELS. TYPE, VOLTAGE, ETC. MCB, MLO |
| ETC.215.5 |
| PLEASE SEE FOLLOWING COMMENTS. |
| |
| 4)NOTE: PLEASE SHOW AND IDENTIFY ALL |
| PANELS, DISCONNECTS ETC ON PLANS. |
| COULD NOT LOCATE DISCONNECT SHOWN ON |
| RISER FOR PANEL "C" ON PLANS. |
| COULD NOT LOCATE POOL PANEL? |
| PLEASE SEE NEXT COMMENT. |
| |
| 5)NOTE: PLEASE SEE PLANS WHICH INDICATE |
| METER/MAIN AT DETACHED BLDG, HOWEVER |
| PANEL "C" SEEMS TO BE SHOWN WITH THE |
| GROUNDING ELECTRODE SYSTEM WHICH IS |
| ACTUALLY REQUIRED FOR PANELS "A" AND "B" |
| AT MAIN HOUSE. |
| 250.32 |
| |
| 6)NOTE: PLEASE SEE PANELS AT MAIN HOUSE |
| SHALL INDICATE MAIN CIRCUIT BREAKER(S) |
| (MCB) FOR DISCONNECTING MEANS AT MAIN |
| HOUSE.225.31 |
| THE GROUNDING ELECTRODE ATTACHMENTS FROM |
| PREVIOUS NOTE SHALL BE ATTACHED TO THESE |
| PANELS. |
| |
| 7)NOTE: PLEASE SEE 400A METER/MAIN SHALL |
| INDICATE 400A MCB. PLEASE SEE ONE 200A |
| BRKR IN THIS PANEL IS SHOWN AS MAIN |
| BREAKER?? |
| PLEASE ALSO SEE PANEL "C" IS NOT |
| SHOWN/IDENTIFIED ON SCHEDULE FOR |
| METER/MAIN. |
| 215.5 |
| |
| 8)NOTE: PLEASE SEE PLANS FOR NUMEROUS |
| SMOKE DETECTORS MISSING. |
| PLEASE SEE NFPA-72 11.5.1.1 WHICH |
| REQUIRES SD'S INSIDE AND OUTSIDE ALL |
| SLEEPING RMS OR ADAPTABLE SLEEPING |
| RMS(THOSE WITH BATHS OR CLOSETS). |
| PLEASE SEE SD'S REQUIRED ON ALL LEVELS |
| OF A MULTI-LEVEL DWELLING. |
| PLEASE SEE SD IN MASTER BEDRM SAHLL BE |
| REQUIRED AT FIRST FLR AND SECOND FLR. |
| SINCE THIS IS AN OPEN RM, SD FOR FIRST |
| FLR SHALL BE WALL MOUNTED IN THE |
| VICINITY OF STAIRS LEADING TO FLR ABOVE. |
| PLEASE ALSO SEE AREA FOR OTHER STAIRS |
| LEADING TO FLR ABOVE. MAIN HOUSE, |
| DETACHED CABANA. |
| PLEASE SEE SD'S HAVE BEEN REDLINED ON |
| PLANS FOR ALL LOCATIONS REQUIRED. |
| |
| 9)NOTE: PLEASE SEE 210.8A2, WHICH |
| REQUIRES ALL RECEPTS IN GARAGE TO BE |
| GFI. |
| |
| 10)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| FOR A/C EQUIPMENT. |
| 210.8A, 210.63 |
| |
| 11)NOTE: PLEASE SEE NUMEROUS GFI RECEPTS |
| MISSING ALONG KITCHEN COUNTERSPACES. |
| 210.8A6, 210.52C1-5 |
| PLEASE SEE A GFI WILL BE REQUIRED ON 2ND |
| FLR "NOOK" AREA OF CABANA ALSO ABOVE |
| DISHWASHER. |
| |
| 12)NOTE: PLEASE SEE NUMEROUS MISSING |
| RECEPTS REQUIRED PER 210.52. 2', 6', 12' |
| OF WALL SPACES. |
| PLEASE SEE RAIL AREA AT 2ND FLR IS |
| CONSIDERED WALL SPACE AND FLR RECEPTS |
| WILL BE REQUIRED PER 210.52 |
| PLEASE CLARIFY AREA T SUNK-IN LIV RM |
| NEXT TO FIRE PLACE. ?? WALL SPACE?? |
| PLEASE SEE MANY OF THE ABOVE HAVE BEEN |
| REDLINED ON PLANS WHERE REQUIRED. MANY |
| OF MISSING. |
| |
| 13)NOTE: PLEASE SEE MISSING HALLWAY |
| RECEPTS PER 210.52H |
| REDLINED. |
| |
| 14)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| PER 210.52D,210.11C3,210.8 |
| |
| 15)NOTE: PLEASE SEE ALL RECEPTS WITIN 6' |
| OF SINKS SHALL BE GFI/GFI PROTECTED. |
| (LAUNDRY RM )210.8A |
| |
| 16)NOTE:PLEASE SEE MISSING EGRESS |
| LIGHTING CONTROL AT LOCATION OF MASTER |
| BEDRM, HALL/LIVING RM ETC. |
| 210.70 |
| PLEASE CORRELATE SWITCHES SHOWN FOR |
| MASTER BEDRM LTS, SCONCES ETC. |
| STAIR-WAY LT CONTROL. GRADE LEVEL |
| ACCESS. MOST HAVE BEEN REDLINED ON PLANS |
| AT LOCATIONS MENTIONED. |
| LS 101 7.8 |
| |
| 17)NOTE: PLEASE LIST THE REQUIRED |
| DEDICATED BATH(S) CIRCUIT(S) PER |
| 210.52D,210.11C3. PLEASE SEE THESE ARE |
| REQUIRED TO BE 20A AND #12 AWG. |
| |
| 18)NOTE: PLEASE SEE NO SWITCHES SHALL BE |
| LOCATED WITHIN THE 3' ZONE OF A |
| TUB/JACUZZI TUB. PLEASE SEE NO RECEPTS |
| SHALL BE LOCATED WITH 3' OF TUB. |
| PLEASE SEE REDLINED PLANS FOR MASTER |
| BATH RM LT CONTROLS, BEDRM #3. |
| 680.71, 410.4 |
| |
| 19)NOTE: PLEASE SEE SYMBOL FOR JACUZZI |
| TUB/WHIRLPOOL TUB IS BEING SHOWN AS |
| 220V, HOWEVER THIS IS NOT LOCATED ON |
| PANEL SCHEDULE(S) OR LOAD CALCS?? |
| PLEASE SEE 680.71, FOR REQUIRED GFI |
| PROTECTION. |
| PLEASE ALSO ADJUST LOAD CALCS. |
| |
| 20)NOTE: PLEASE SEE A GDO IS SHOWN ON |
| LOAD CALCS FOR PANELS LOCATED ON MAIN |
| HOUSE,HOWEVER NO GDO COULD BE LOCATED AT |
| MAIN HOUSE? |
| PLEASE SEE DETACHED "GARAGE" DOES NOT |
| INDICATE OR SHOW A GARAGE DOOR OR GDO. |
| PLEASE INCLUDE IN PANEL "C" , LOADS ETC. |
| 215.5 |
| |
| 21)NOTE: PLEASE SEE MISSING DISCONNECTS |
| REQUIRED FOR WATER HEATERS. |
| 422.31 |
| |
| 22)NOTE: PLEASE SEE MISSING |
| DISCONNECTING MEANS REQUIRED FOR AHU'S , |
| PER 440.11 |
| PLEASE SEE MIN CLEARENCES REQUIRED PER |
| 110.26. |
| PLEASE ALSO SEE DISCONNECT CLEARENCE |
| REQUIRED FOR CU'S OUTSIDE. |
| PLEAS ADJUST. |
| |
| 23)NOTE: PLEASE CORRELATE ALL A/C LOADS |
| ON LOAD CALCS, NUMBER OF UNITS INDICATED |
| ON PANEL SCHEDULE(S) AND NUMBER OF UNITS |
| SHOWN ON PLANS. |
| PLEASE SEE LOAD CALCS FOR MAIN HOUSE |
| INDICATE 4-5 AHU'S??? WHEREAS PLANS SHOW |
| 3-CU'S AND PANEL SCHEDULES ONLY INDICATE |
| 2 UNITS TOTAL??? |
| 215.5 ETC. |
| |
| 24)NOTE: PLEASE SEE PREVIOUS NOTE, ONCE |
| A/C UNITS HAVE BEEN CORRELATED, PLEASE |
| SEE 424.3B FOR MIN OCP OF 125% OF HEAT |
| KW LOAD. PLEASE ALSO NOTE, MAX OCP OF |
| 150% |
| PLEASE ADJUST OCP AND CONDUCTORS AS |
| LISTED ON PLANS. |
| PLEASE SEE LOAD CALCS AND KW RATING |
| SHOWN. |
| |
| 25)NOTE: PLEASE PROVIDE LOADS ON EACH |
| PANEL.PLEASE SEE MISSING POOL PANEL, |
| PANEL SCHEDULE. LOADS ARE SHOWN ON MAIN |
| CALCS, HOWEVER THESE LOADS CAN NOT BE |
| VERIFIED. |
| PLEASE KNOW, ALL CONTINUOUS LOADS SHALL |
| BE SHOWN AT 125%. (3 OR MORE HRS). |
| POOL PUMP, HEAT PUMPS? |
| 215.3,230.42 ETC. |
| |
| 26)NOTE: PLEASE SEE 250.66, 310.15B6 FOR |
| MIN GROUNDING ELECTRODE CONDUCTOR. |
| PLEASE SEE 1/0 MIN AT MAIN SERVICE AT |
| DETACHED GARAGE. PLEASE ALSO SEE MIN AT |
| MAIN HOUSE SHALL BE #2 |
| |
| 27)NOTE: PLEASE CORRELATE ALL DEDICATED |
| CIRCUITS WHICH ARE SHOWN ON PLANS, |
| HOWEVER NOT ALL ARE LISTED ON PANEL |
| SCHEDULES. |
| COULD NOT LOCATE ELEC OVEN ON PLANS? |
| PLEASE MOVE ANY 220V OUTLETS FOR |
| OVENS/RANGES DIRECTLY BEHIND UNITS. |
| PLEASE SEE PLANS SHOW TWO RANGES, HOWEVR |
| PANEL SCHEDULE ONLY SHOWS ONE?? |
| PLEASE SEE ZONING NOTES. |
| PLEASE SEE # OF ICE MAKERS LISTED ON |
| LOAD CALCS, YET ONLY ONE DEDICATED |
| CIRCUIT IS SHOWN ON PANEL SCHEDULE? |
| PLEASE CORRELATE OTHERS. |
| |
| 28)NOTE: PLEASE VERIFY WHAT APPEARS TO |
| BE A 220V RECEPT SHOWN IN PANTRY.?? |
| PLEASE ALSO CALRIFY RECEPTS SHOWN IN |
| CLOSETS? ABOVE? BELOW? COMBUSTIBLES.? |
| PLEASE BE AWARE OF INTENDED USE OF THESE |
| WHICH MAY NOT PERMIT THESE TO BE LOCATED |
| IN CLOSETS. |
| 240.24 ETC |
| |
| 29)NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 30)NOTE: PLEASE SEE DISHWASHER IS SHOWN |
| ON PLANS FOR CABANA, HOWEVER PANEL |
| SCHEDULE AND LOAD CALCS DO NOT INDICATE |
| THE SAME.?? |
| PLEASE ALSO SEE MICROWAVE SHOWN ON PANEL |
| SCHEDULE, BUT NOT ON PLANS FOR DEDICATED |
| CIRCUIT?? |
| |
| 31)NOTE: PLEASE SEE GFI SHOWN ON |
| COUNTERSPACE IN DETACHED CABANA, IS |
| SHOWN AS "WP" ?? THIS IS PERMITTED, |
| HOWEVER NOT REQUIRED. |
| 210.8A6 |
| |
| 32)NOTE: PLEASE IDENTIFY OTHER 220V |
| RECEPTS SHOWN ON PLANS , HOWEVER THESE |
| ARE NO LISTED IN LOAD CALCS OR ON PANEL |
| SCHEDULES?? |
| PLEASE SEE CABANA AND MAIN HOUSE. |
| |
| |
| PLEASE CORRELATE ALL A/C EQUIPMENT WITH |
| MECHANICAL PLANS. |
| THESE DO NOT MATCH. |
| |
| PLEASE KNOW, MANY OF THE ABOVE ITEMS |
| HAVE BEEN REDLINED ON PLANS AT LOCATIONS |
| OF NOTES. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM |
| SETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. PLEASE ONLY SUBMIT ONE SET OF |
| OLD/VOIDED SHEETSREQUIRED FOR |
| REFERENCE. |
| |
| PLEASE SEE ANY COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS , |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REIVEW |