Plan Review Notes For Permit 05091279 |
Permit Number |
05091279 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-10-04 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} INDICATE THE LOCATION OF THE NEW 150 | | AMP PANEL THAT IS ON THE PARTIAL RISER. | | | | 2} THE PENINSULA MUST HAVE A RECEPTACLE | | PER 210.52(C)(3). | | | | 3) THE COUNTER SPACING ON EITHER SIDE OF | | THE MICROWAVE DOES NOT APPEAR TO HAVE | | ENOUGH RECEPTACLES. SEE 210.52(C)(1). | | | | 4} SUBMIT TWO COPIES OF ALL PLANS FPR | | REVIEW PER 104.2.1 FBC. | | | | 5} THE PERSON TAKING RESPONSIBILITY FOR | | THE PLAN MUST PRINT AND SIGN THEIR NAME | | TO ALL SHEETS. ALSO 104.2.1 FBC. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|