2005-10-04 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE LOCATION OF THE NEW 150
 AMP PANEL THAT IS ON THE PARTIAL RISER.
  
 2} THE PENINSULA MUST HAVE A RECEPTACLE
 PER 210.52(C)(3).
  
 3) THE COUNTER SPACING ON EITHER SIDE OF
 THE MICROWAVE DOES NOT APPEAR TO HAVE
 ENOUGH RECEPTACLES. SEE 210.52(C)(1).
  
 4} SUBMIT TWO COPIES OF ALL PLANS FPR
 REVIEW PER 104.2.1 FBC.
  
 5} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT AND SIGN THEIR NAME
 TO ALL SHEETS. ALSO 104.2.1 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  