Plan Review Notes
Plan Review Notes For Permit 05091241
Permit Number 05091241
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-22 00:00:00BUILDING REVIEW CHECKLIST:
 1- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS IF WORK IS NOT STARTED.
 NEED RE-RECORDED NOC.
  
 2- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR:
 A) ACCORDION SHUTTERS, B) ALUMINUM
 PANELS AND C) STEEL PANELS AS REQUIRED
 BY RULE 9B-72 OF DCA. SEE THE WEBSITE
 WWW.FLORIDABUILDING.ORG FOR REQUIRED
 INFORMATION. DADE COUNTY NOA ALONE IS
 NOT AUTOMATICALLY AN STATE WIDE FLORIDA
 PRODUCT APPROVAL.
  
 3- KEY PLAN AND INSTALLATION SCHEDULE
 DON'T MATCH. REVISE AS REQUIRED.
  
 4- INSTALLATION SCHEDULE: CLEARLY
 INDICATE WHICH OPENINGS WILL HAVE STEEL
 PANELS, ALUMINUM PANELS OR ACCORDION
 SHUTTERS AND CLEARLY SPECIFY ANCHOR TYPE
 FOR EACH OPENING. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 5- CONTRACTOR TO UPDATE WORKER'S COMP.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.