Plan Review Notes
Plan Review Notes For Permit 05091240
Permit Number 05091240
Review Stop B
Sequence Number 3
Notes
Date Text
2006-07-18 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- ENGINEERING CALCS COMMENTS FROM
 PREVIOUS CHECKLIST:
 A) ENGINEER TO GET CORRECT BUILDING
 DIMENSIONS FOR BUILDING MEAN HEIGHT,
 CLADDING ELEVATION AND BUILDING WIDTH
 AND REVISE CALCULATIONS AS REQUIRED.
 B) FLORIDA BUILDING CODE 2004 REFERS TO
 ASCE 7-02, NOT ASCE 7-98. REVISE
 CALCULATIONS AS REQUIRED.
 NOTE; ENGINEER TO GET ALL CORRECT
 INFORMATION TO PROPERLY MAKE HIS SITE
 SPECIFIC CALCULATIONS.
  
 2- REVISE INSTALLATION SCHEDULE:
 A) STRUCTURE TO RECEIVE PANELS IS
 CONCRETE BLOCK, NOT CONCRETE. REVISE AS
 REQUIRED AND SEE DRAWING 7 OF 7 OF STORM
 SHUTTERS FOR PROPER ANCHOR SPACING.
 B) CLARIFY WHY OPENING #2 IS 74" WIDE
 BUT SHUTTER SPAN IS 73"?.
 C) CLARIFY WHAT IS THE SPECIFIC
 MOUNTING CONDITIONS. STORM SHUTTER DWGS
 ARE MARKED WITH ALL KIND OF MOUNTING
 CONDITIONS AND THERE ARE ONLY TWO
 OPENINGS TO BE CLOSED.
 F) IF USING DIRECT MOUNT APPLICATION,
 THEN NEED TO PROVIDE REMOVABLE ANCHORS.
 TAPCONS ARE NOT REMOVABLE ANCHORS.
  
 3- STORM PANELS DRAWING 7 OF 7 IS MARKED
 WITH DIFFERENT ANCHOR TYPES AND SPACING.
 THIS DOESN'T MATCH THE INSTALLATION
 SCHEDULE. REVISE AS REQUIRED.
  
 4- OWES $50 FOR RE-SUBMITTAL FEES. THIS
 IS THE THIRD TIME THIS APPLICATION IS
 BEEN REVIEWED. ADDITIONAL FEES ARE DUE
 WHEN RE-SUBMITTING APPLICATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712