2006-05-23 00:00:00 | BUILDING REVIEW SECOND CHECKLIST: |
| |
| 1- PERMIT APPLICATION WAS NOT SUBMITTED |
| WITH THE RE-SUBMITTAL PACKGAGE. NEED TO |
| PROVIDE THE PERMIT APPLICATION TO |
| PROCESS THE PERMIT. |
| |
| 2- PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE ATTACHED SAMPLE. |
| |
| 3- ENGINEERING CALCS: |
| A) ENGINEER TO GET CORRECT BUILDING |
| DIMENSIONS FOR BUILDING MEAN HEIHGT, |
| CLADDING ELEVATION AND BUILDING WIDTH |
| AND REVISE CALCULATIONS AS REQUIRED. |
| B) FLORIDA BUILDING CODE 2004 REFERS |
| TO ASCE 7-02, NOT ASCE 7-98. REVISE |
| CALCULATIONS AS REQUIRED. |
| |
| 4- STORM SHUTTERS DON'T MEET THE DESIGN |
| PRESURES CALCULATED BY THE ENGINEER. |
| NEED STORM SHUTTERS THAT MEET OR EXCEED |
| CALCULATED DESIGN PRESSURES. |
| ***NOTE: ENGINEER CALCULATIONS WERE DONE |
| USING EXPOSURE C. THIS BUILDING IS |
| LOCATED IN EXPOSURE B. THIS IS WHY THE |
| DESIGN PRESSURES ARE HIGHER. IF ENGINEER |
| WANTS HE CAN REVISE HIS CALCULATIONS |
| USING THE EXPOSURE B TO LOWER THE DESIGN |
| PRESSURES. |
| |
| 5- PERMIT PLOT PLAN SHEET: REVISE |
| BUILDING DIMENSIONS TO MATCH EXISTING |
| BUILDING. |
| |
| 6- EVERY SHEET SIGNED BY THE ENGINEER TO |
| HAVE ORIGINAL SEAL, SIGNATURE AND DATE |
| AS REQUIRED BY CHAPTER 471 FLORIDA |
| STATUTE AND FLORIDA ADMINISTRATIVE CODE. |
| THREE SETS SUBMITTED, BUT ONLY TWO HAD |
| ORIGINAL SEAL AND SIGNATURE. |
| |