2006-05-23 00:00:00BUILDING REVIEW SECOND CHECKLIST:
  
 1- PERMIT APPLICATION WAS NOT SUBMITTED
 WITH THE RE-SUBMITTAL PACKGAGE. NEED TO
 PROVIDE THE PERMIT APPLICATION TO
 PROCESS THE PERMIT.
  
 2- PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 3- ENGINEERING CALCS:
 A) ENGINEER TO GET CORRECT BUILDING
 DIMENSIONS FOR BUILDING MEAN HEIHGT,
 CLADDING ELEVATION AND BUILDING WIDTH
 AND REVISE CALCULATIONS AS REQUIRED.
 B) FLORIDA BUILDING CODE 2004 REFERS
 TO ASCE 7-02, NOT ASCE 7-98. REVISE
 CALCULATIONS AS REQUIRED.
  
 4- STORM SHUTTERS DON'T MEET THE DESIGN
 PRESURES CALCULATED BY THE ENGINEER.
 NEED STORM SHUTTERS THAT MEET OR EXCEED
 CALCULATED DESIGN PRESSURES.
 ***NOTE: ENGINEER CALCULATIONS WERE DONE
 USING EXPOSURE C. THIS BUILDING IS
 LOCATED IN EXPOSURE B. THIS IS WHY THE
 DESIGN PRESSURES ARE HIGHER. IF ENGINEER
 WANTS HE CAN REVISE HIS CALCULATIONS
 USING THE EXPOSURE B TO LOWER THE DESIGN
 PRESSURES.
  
 5- PERMIT PLOT PLAN SHEET: REVISE
 BUILDING DIMENSIONS TO MATCH EXISTING
 BUILDING.
  
 6- EVERY SHEET SIGNED BY THE ENGINEER TO
 HAVE ORIGINAL SEAL, SIGNATURE AND DATE
 AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE AND FLORIDA ADMINISTRATIVE CODE.
 THREE SETS SUBMITTED, BUT ONLY TWO HAD
 ORIGINAL SEAL AND SIGNATURE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712