2005-11-22 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY RULE 9B-72 OF DCA SINCE OCT.
 1ST 2004. SEE WWW.FLORIDABUILDING.ORG
 FOR COMPLETE REQUIREMENTS FOR PRODUCT
 APPROVAL.
  
 2- PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 3- ENGINEERED DESIGN WIND LOADS CHART IS
 MARKED INCORRECTLY. THIS IS AN EIGHT
 STORY BUILDING. THEREFORE MEAN ROOF
 HEIGHT CAN'T BE 15'-0". ENGINEER TO
 CLEARLY INDICATE DESIGN CRITERIA THAT
 APPLIES TO THIS BUILDING. ALSO, REVISE
 INFORMATION ON PERMIT PLOT PLAN SHEET.
 REVISE MEAN ROOF HEIGHT AND BUILDING
 DIMENSIONS TO MATCH ACTUAL BUILDING.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001.
  
 4- CONTRACTOR TO UPDATE WORKER'S
 COMPENSATION.
  
 5- TABLE 1, STORM PANEL SPAN SCHEDULE ON
 SHEET 3 OF 4 OF ENGINERED DRAWINGS:
 DESIGN LOAD OF 43PSF DOESN'T MATCH
 DESIGN LOAD SPECIFIED ON ENGINEER'S
 DESIGN LOAD CHART. REVISE AS REQUIRED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001.
  