2005-11-22 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- PROVIDE FLORIDA PRODUCT APPROVAL OR |
| APPLY FOR LOCAL PRODUCT APPROVAL AS |
| REQUIRED BY RULE 9B-72 OF DCA SINCE OCT. |
| 1ST 2004. SEE WWW.FLORIDABUILDING.ORG |
| FOR COMPLETE REQUIREMENTS FOR PRODUCT |
| APPROVAL. |
| |
| 2- PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE ATTACHED SAMPLE. |
| |
| 3- ENGINEERED DESIGN WIND LOADS CHART IS |
| MARKED INCORRECTLY. THIS IS AN EIGHT |
| STORY BUILDING. THEREFORE MEAN ROOF |
| HEIGHT CAN'T BE 15'-0". ENGINEER TO |
| CLEARLY INDICATE DESIGN CRITERIA THAT |
| APPLIES TO THIS BUILDING. ALSO, REVISE |
| INFORMATION ON PERMIT PLOT PLAN SHEET. |
| REVISE MEAN ROOF HEIGHT AND BUILDING |
| DIMENSIONS TO MATCH ACTUAL BUILDING. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| 2001. |
| |
| 4- CONTRACTOR TO UPDATE WORKER'S |
| COMPENSATION. |
| |
| 5- TABLE 1, STORM PANEL SPAN SCHEDULE ON |
| SHEET 3 OF 4 OF ENGINERED DRAWINGS: |
| DESIGN LOAD OF 43PSF DOESN'T MATCH |
| DESIGN LOAD SPECIFIED ON ENGINEER'S |
| DESIGN LOAD CHART. REVISE AS REQUIRED. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| 2001. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |