2005-09-28 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- DESCRIPTION OF WORK IN PERMIT |
| APPLICATION SAYS "INSTALL BACKWALL |
| PANELS" AND PRODUCT APPROVAL SUBMITTED |
| IS FOR WALL PANELS. ACCORDING TO THE |
| ROOFING CONTRACTOR SCOPE OF WORK (SEE |
| ATTACHED COPY FROM DBPR) WALL PANELS ARE |
| OUT OF THE ROOFING CONTRACTOR SCOPE OF |
| WORK. NEED LICENSED CONTRACTOR WHO'S |
| SCOPE OF WORK LICENSE ALLOWS TO DO WALL |
| PANELS TO PULL OUT THE PERMIT. |
| |
| 3- PROVIDE COMPLETE DETAILS AND SPECS TO |
| SHOW INSTALLATION OF WALL PANELS |
| INCLUDING AREA OF THE BUILDING WHERE |
| PANELS WILL BE INSTALLED. DRAWINGS TO BE |
| SIGNED AND SEALED BY THE PROFESSIONAL |
| DESIGNER. SEC. 104.2.1.2 CITY AMENDMENTS |
| TO FBC 2001. |
| |
| 4- ENGINEER USED DADE COUNTY NOA |
| 01-0417.12 AS A REFERENCE FOR HIS |
| CALCULATIONS. FLORIDA PRODUCT APPROVAL |
| FL1904 DOESN'T INCLUDE THIS DADE COUNTY |
| NOA AS THE REPORT SUBMITTED FOR FLORIDA |
| PRODUCT APPROVAL. THE REPORT THAT WAS |
| SUBMITTED FOR FLORIDA PRODUCT APPROVAL |
| WAS AN EVALUATION REPORT BY ANOTHER |
| ENGINEER. NEED TO USE SAME REPORT THAT |
| WAS SUBMITTED FOR FLORIDA PRODUCT |
| APPROVAL. OTHERWISE, ANOTHER PRODUCT |
| APPROVAL SHALL BE USED. |
| ACCORDING TO THE BUILDING OFFICIAL DADE |
| COUNTY NOA ALONE IS NOT AUTOMATICALLY AN |
| STATEWIDE FLORIDA PRODUCT APPROVAL. SEE |
| RULE 9B-72 IN WWW.FLORIDABUILDING.ORG. |
| MANUFACTURER MAY APPLY FOR LOCAL PRODUCT |
| APPROVAL USING THE DADE COUNTY NOA AND |
| COMPLETING THE LOCAL PRODUCT APPROVAL |
| FORM DOWNLOADED FROM |
| WWW.FLORIDABUILDING.ORG. |
| |
| 5- ENGINEER TO PROVIDE ALL HIS |
| INFORMATION WHEN SIGNING AND SEALING |
| DOCUMENTS AS REQUIRED BY CHAPTER 471 FL |
| STATUTES AND FAC 61G15-23.002. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712. |