Plan Review Notes For Permit 05091161 |
Permit Number |
05091161 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-22 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- PROVIDE COMPLETE INSTALLATION | | SCHEDULE. SEE ATTACHED SAMPLE. | | | | 2- DESIGN PRESSURES INDICATED ON THE | | WIND LOAD CHART TAKEN FROM THE FBC 2001 | | ARE INCORRECT. THE EFFECTIVE AREA | | (TRIBUTARY AREA FOR THE ANCHORS) SHALL | | BE 10PSF NOT 100PSF. REVISE AS REQUIRED. | | OR PROVIDE COMPLETE ENGINEERING ANALYSIS | | STATING WHY USING THE 100PSF AS THE | | EFFECTIVE WIND AREA. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | | | 3- ANCHOR SCHEDULE IN STORM PANELS | | ENGINEERED DRAWINGS: A) REVISE MARKED | | ANCHOR TYPE AND SPACING TO BE USED | | ACCORDING TO THE REVISED DESIGN | | PRESSURES REQUESTED ON ITEM #2 ABOVE. | | B) CIRCLE ONLY THE ANCHOR TYPE AND | | SPACING THAT APPLY TO THIS JOB. | | | | 4- CONTRACTOR TO UPDATE LICENSE WITH THE | | FRONT COUNTER PERMIT SPECIALISTS. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|