Plan Review Notes For Permit 05091155
Permit Number 05091155
Review Stop M
Sequence Number 2
Notes
Date Text
2005-10-06 00:00:00*** PROVISO ***
 1) RETURN AIR TRANSFER DUCTS NEED TO BE
 1 1/2 TIMES LARGER THAN SUPPLY AIR
 DUCTS, PER 2001 FBC/M 601.4 . PLECSE
 MAKE RETURN DUCTS 10" .