Plan Review Notes For Permit 05091147 |
Permit Number |
05091147 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-26 00:00:00 | 1. PLANS DO NOT INDICATE EXISTING | | EXIT SIGNS OR EMERGENCY LIGHTS. | | | | 2. NO WALL DETAILS ILLUSTRATED FOR | | THE DRAWINGS. | | | | 3. NO PORTABLE FIRE EXTINGUISHERS SHOWN. | | | | 4. PLANS LACK SUFFICIENT DETAIL TO | | PERFORM PROPER REVIEW. | | | | 5. SEVERAL NEW DOORS SHOWN BUT NO SIZES | | OR HARDWARE INFORMATION PROVIDED. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | | | 804-4709 PHONE | | 804-4774 FAX |
|