Plan Review Notes For Permit 05091147 |
Permit Number |
05091147 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-10-03 00:00:00 | ********* UNSAT ********* | | | | 1)NOTE: PLEASE INDICATE AND SHOW ANY | | ELECTRICAL IN NEW PROPOSED WALLS AND/OR | | DELETION OF ELECTRICAL IN SCOPE OF WORK. | | | | 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | AND CORRELATE WITH A PANEL SCHEDULE(S) | | TO BE SUBMITTED. SCOPE OF WORK WILL | | DETERMINE WEATHER OR NOT THIS WILL BE | | NEEDED. | | 215.5 | | | | 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS, | | FOR EM/EXT LTS. PLEASE SEE 700.12E FOR | | CIRCUITING OF EM/EXT LTS. | | | | 4)NOTE: PLEASE SEE FBC 104.2.1 WHICH | | REQUIRES THE PRINTED NAME AND SIGNATURE | | OF THE PERSON RESPONSIBLE FOR PLANS/ | | DESIGN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|