Plan Review Notes For Permit 05091007 |
Permit Number |
05091007 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-10-11 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1-A) ENGINEER CALCULATIONS: CLARIFY WHY | | THE EXTERIOR PARTITION DESIGN LOADS | | CHART SHOWS INTERNAL PRESSURE OF 0.00. | | IT'S NOT CLEAR IF THE DESIGN ASSUMPTION | | IS THAT BUILDING IS ENCLOSED OR | | PARTIALLY ENCLOSED SINCE NO VALUE WAS | | ENTERED. ENGINEER TO REVISE/CLARIFY AS | | REQUIRED. SEC. 104.2.1.2 CITY AMENDMENTS | | TO FBC 2001. | | | | B) ENGINEER TO CLARIFY IF DOOR WILL BE | | USED AS PART OF THE BUILDING ENVELOPE OR | | NOT. SEE NOTE REGARDING THE DESIGN | | PRESSURES ON ITEM #3 OF THIS WIND | | CALCULATIONS SHEET WHICH SAYS THAT | | "THESE LOADS ARE NOT INTENDED FOR USE | | WITH COMPONENTS THAT PROTECT OR CREATE A | | BUILDING ENVELOPE". | | | | 2- CLEARLY SPECIFY ON SHEET 2 OF 4 | | SPECIFIC DOOR MODULE AND GLASS TYPE TO | | BE INSTALLED TO VERIFY COMPLIANCE WITH | | THE DESIGN PRESSURES CALCULATED BY THE | | ENGINEER. | | | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712. |
|