Plan Review Notes For Permit 05090956 |
Permit Number |
05090956 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-18 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1. SHTS P2.1.1, P-2.2.4, P-3.1.1, P-3.2 | | AND P-3.2.4 WATER HAMMER ARRESTORS ARE | | REQUIRED AT THE WASH MACHINES OF ALL | | UNITS. PER SECTION 604.9. - ALL WATER | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | THE FIXTURES IN AN "EFFECTIVE RANGE", | | NOT IN THE CEILING AS SHOWN IN SOME | | CASES. PDI-WH 201 AND MANUF INSTALLATION | | INSTRUCTIONS. | | ***RESPONSE NOTED, BUT COMMENT NOT | | ADDRESSED FOR SHEETS P2.1.1, P2.2, (SHT | | NOT INDICATED ON FIRST REVIEW), P3.1.1, | | P3.2, AND P3.2.1, (NOT INDICATED ON | | FIRST REVIEW). | | | | **************NEW COMMENT************** | | | | 1B. SHTS P2.1.1, P3.1, & P3.1.1. THE | | SANITARY BUILDING DRAIN SHALL BE A | | MINIMUM OF 4 FT. OFF THE FOOTER PER | | SECTION 307.4. | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|