2006-06-07 00:00:00 | PROVISO:2001 FBC/BUILDING 5/6 UNITS |
| |
| PLEASE REVISE PLANS TO REFLECT THE |
| IMPLEMENTATION OF THE FOLLOWING |
| PROVISO'S: |
| |
| 1.PLAN SHEET M0.1 THE AHU MOUNTING |
| DETAIL NOTE 15 STATES "NO COMBUSTIBLES |
| ALLOWED IN THE MECHANICAL CLOSET" AS |
| THIS SERVES AS A RETURN AIR PLENUM.THE |
| DOOR SCHEDULE ON PLAN A-4.1.1. INDICATES |
| A WOOD LOUVERED DOOR.PLEASE VERIFY |
| WITH THE DOOR MANUFACTURE THAT THIS |
| MEETS THE REQUIREMENT OF 25 FLAME/50 |
| SMOKE INDEX AS SPECIFIED IN 2001 FMC |
| 602.2.1. |
| |
| 2.OUTSIDE AIR CALCULATIONS INDICATED |
| ON M0.1 ARE BASED ON INFILTRATION RATES. |
| THE INFILTRATION RATES ARE THE "MAXIMUM" |
| ALLOWED BY CODE & MAY NOT BE A |
| "TRUE/ACTUAL" RATE.PLEASE PROVIDE |
| CALCS IN ACCORDANCE WITH 2001 FMC |
| 402.2., 402.2.1 OR TABLE 403.3.PLEASE |
| NOTE, PLAN SHEET M2 INDICATES A 6" O.A. |
| DUCT, IF THIS IS NOT UTILIZED, PLEASE |
| REMOVE FROM THE PLANS. |
| |
| 3.SPECIFIC DRYERS ARE TO BE INSTALLED |
| BY FINAL INSPECTION. |
| |
| 4.RETURN AIR INDICTED ON THE FIRST |
| FLOOR BETWEEN THE GARAGE AND THE FOYER |
| DOOR IS NOT REQUIRED PER 2001 FMC 601.4 |
| EXCEPTION #3, AS THIS IS NOT A HABITABLE |
| SPACE. |
| |