2006-06-07 00:00:00 | PROVISO:2001 FBC/BUILDING 4/6 UNITS |
| |
| PLEASE REVISE PLANS TO REFLECT THE |
| IMPLEMENTATION OF THE FOLLOWING |
| PROVISO'S: |
| |
| 1.PLAN SHEET M0.1 THE AHU MOUNTING |
| DETAIL NOTE 15 STATES "NO COMBUSTIBLES |
| ALLOWED IN THE MECHANICAL CLOSET" AS |
| THIS SREVES AS A RETURN AIR PLENUM.THE |
| DOOR SCHEDULE ON PLAN A-4.1.1 INDICATES |
| A WOOD LOUVERED DOOR.PLEASE VERIGY |
| WITH THE DOOR MANUFACTURE THAT THIS |
| MEETS THE REQUIREMENT OF 25 FLAME/50 |
| SMOKE INDEX AS SPECIFIED IN 2001 FMC |
| 602.2.1. |
| |
| 2.OUTSIDE AIR CALCULATIONS INDICATED |
| ON M0.1 ARE BASED ON INFILTRATION RATES. |
| THE INFILTRATION RATES ARE THE "MAXIMUM" |
| ALLOWED BY CODE & MAY NOT BE A |
| "TRUE/ACTUAL" RATE.PLEASE PROVIDE O.A. |
| CALCS IN ACCORDANCE WITH 2001 FMC 402.2, |
| 402.2.1 OR TABLE 403.3.PLEASE NOTE, |
| PLAN SHEET M2 INDICATES A 6" O.A. DUCT, |
| IF THIS IS NOT UTILIZED PLEASE REMOVE |
| FROM THE PLANS. |
| |
| 3.SPECIFIC DRYERS ARE TO BE INSTALLED |
| BY FINAL INSPECTION. |
| |
| 4.RETURN AIR INDICATED ON THE FIRST |
| FLOOR (M1) BETWEEN THE GARAGE AND THE |
| FOYER DOOR IS NOT REQUIRED PER2001 FMC |
| 601.4 EXCEPTION #3, AS THIS IS NOT A |
| HABITABLE SPACE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561)805-6719. |