2006-06-07 00:00:00PROVISO:2001 FBC/BUILDING 4/6 UNITS
  
 PLEASE REVISE PLANS TO REFLECT THE
 IMPLEMENTATION OF THE FOLLOWING
 PROVISO'S:
  
 1.PLAN SHEET M0.1 THE AHU MOUNTING
 DETAIL NOTE 15 STATES "NO COMBUSTIBLES
 ALLOWED IN THE MECHANICAL CLOSET" AS
 THIS SREVES AS A RETURN AIR PLENUM.THE
 DOOR SCHEDULE ON PLAN A-4.1.1 INDICATES
 A WOOD LOUVERED DOOR.PLEASE VERIGY
 WITH THE DOOR MANUFACTURE THAT THIS
 MEETS THE REQUIREMENT OF 25 FLAME/50
 SMOKE INDEX AS SPECIFIED IN 2001 FMC
 602.2.1.
  
 2.OUTSIDE AIR CALCULATIONS INDICATED
 ON M0.1 ARE BASED ON INFILTRATION RATES.
 THE INFILTRATION RATES ARE THE "MAXIMUM"
 ALLOWED BY CODE & MAY NOT BE A
 "TRUE/ACTUAL" RATE.PLEASE PROVIDE O.A.
 CALCS IN ACCORDANCE WITH 2001 FMC 402.2,
 402.2.1 OR TABLE 403.3.PLEASE NOTE,
 PLAN SHEET M2 INDICATES A 6" O.A. DUCT,
 IF THIS IS NOT UTILIZED PLEASE REMOVE
 FROM THE PLANS.
  
 3.SPECIFIC DRYERS ARE TO BE INSTALLED
 BY FINAL INSPECTION.
  
 4.RETURN AIR INDICATED ON THE FIRST
 FLOOR (M1) BETWEEN THE GARAGE AND THE
 FOYER DOOR IS NOT REQUIRED PER2001 FMC
 601.4 EXCEPTION #3, AS THIS IS NOT A
 HABITABLE SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.