Plan Review Notes For Permit 05090955 |
Permit Number |
05090955 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-14 00:00:00 | ******* NOTES REDINED,******* | | ** PLANS ARE TO BE REVISED. ***** | | | | ** PLEASE SEE SOME COMMENTS FROM | | PREVIOUS REVIEW AND SOME NEW COMMENTS | | DUE TO CHANGES IN PLANS. | | | | 1) NOTE: PLEASE SEE MIN OCP FOR AHU | | HEAT, SHALL BE SIZED PER 424.3B , 125% | | MIN. | | PLEASE SEE 40A OCP NOW SHOWN???? | | | | 2) NOTE: PLEASE SEE NO SEC'S ARE SHOWN | | ON RISER FROM FPL TO NEW 1000A SERVICE?? | | SEC'S ARE SHOWN INAIC | | CALCS.240.4,310.16, 215.5 ETC. | | | | 3) NOTE: PLEASE SEE MIN GEC SHALL BE | | SIZED PER 250.66. A #4 IS STILL SHOWN, | | THIS WAS FROM PREVIOUS PLANS AND NEEDS | | TO BE ADJUST WHEN SEC'S ARE SIZED. | | PLEASE SEE 3/0 MIN. | | | | IF PLANS COME BACK FOR ANY OTHER | | COMMENTS, REVISE AT THAT TIME. IF PLANS | | PASS ALL TRADES THIS REVIEW, REVISE | | BEFORE ANY ROUGH SLAB INSPECTION. | | INCLUDING SLAB. |
|