2006-05-14 00:00:00******* NOTES REDINED,*******
 ** PLANS ARE TO BE REVISED. *****
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SOME NEW COMMENTS
 DUE TO CHANGES IN PLANS.
  
 1) NOTE: PLEASE SEE MIN OCP FOR AHU
 HEAT, SHALL BE SIZED PER 424.3B , 125%
 MIN.
 PLEASE SEE 40A OCP NOW SHOWN????
  
 2) NOTE: PLEASE SEE NO SEC'S ARE SHOWN
 ON RISER FROM FPL TO NEW 1000A SERVICE??
 SEC'S ARE SHOWN INAIC
 CALCS.240.4,310.16, 215.5 ETC.
  
 3) NOTE: PLEASE SEE MIN GEC SHALL BE
 SIZED PER 250.66. A #4 IS STILL SHOWN,
 THIS WAS FROM PREVIOUS PLANS AND NEEDS
 TO BE ADJUST WHEN SEC'S ARE SIZED.
 PLEASE SEE 3/0 MIN.
  
 IF PLANS COME BACK FOR ANY OTHER
 COMMENTS, REVISE AT THAT TIME. IF PLANS
 PASS ALL TRADES THIS REVIEW, REVISE
 BEFORE ANY ROUGH SLAB INSPECTION.
 INCLUDING SLAB.