2006-02-07 00:00:00DENIED:BUILDING 10 / 2001 FBC
 1.PLAN SHEET A-0.0.0 PRODUCT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED SPRINKLERED.PLEASE
 INDICATE WHICH SYSTEM WILL BE UTILIZED -
 (13, 13R, 13D, ETC).PLEASE NOTE,
 ADDITIONAL COMMENTS MAY BE GENERATED BY
 THE RESPONSE GIVEN.
  
 2.PLAN SHEET M1 INDICATES EXHAUST DUCT
 PENETRATING FIRE RATED WALLS.PLEASE
 SHOW COMPLIANCE WITH 2001 FMC 607.1.3 #3
 ITEMS 1 THROUGH 4.
  
 3.PLAN SHEET M1 UNIT #88 R/A JUMPER
 FROM THE GUEST SUITE IS NOT SIZED
 PROPERLY.R/A SHOULD BE A MINIMUM OF
 12".PLEASE REVISE.
  
 4.R/A TRANSFER GRILLES ARE NOT SIZE
 PROPERLY.PLEASE REFERENCE 2001 FMC
 601.4 EXCEPTION #2 & 3 AND SIZE GRILLES
 ACCORDINGLY.
  
 3.PLAN SHEET M3 THE DRYER EXHAUST
 DUCTS EXCEED THE 25FT REQUIREMENT WITH
 REDUCTIONS FOR THE 90'S PER 2001 FMC
 504.6.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001 FMC
 TABLE 403.3.
  
 6.PLEASE PROVIDE DETAIL FOR THE AHU
 LOCATED IN THE CLOSET.PLEASE NOTE,
 MECHANICAL CLOSET SHALL COMPLY WITH 2001
 FMC 603.9 & 610.1.ABC.3.7 OF CHAPTER 13
 OF THE 2001 FBC.
  
 7.CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" AWAY FROM THE BUILDING STRUCTURE
 PER 2001 FBC 1503.4.4.
  
 8.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FMC
 307.2.3.
  