Date |
Text |
2005-11-30 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1. SHTS P2.1.1, P2.2, P-2.2.4, P-3.1.1, | | P-3.2 AND P-3.2.4 WATER HAMMER ARRESTORS | | ARE REQUIRED AT THE WASH MACHINES OF ALL | | UNITS. PER SECTION 604.9. - ALL WATER | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | THE FIXTURES IN AN "EFFECTIVE RANGE", | | NOT IN THE CEILING AS SHOWN IN SOME | | CASES. PDI-WH 201 AND MANUF INSTALLATION | | INSTRUCTIONS. | | 2. IF INDIVIDUAL METERS NO BACKFLOW | | DEVISE IS REQUIRED, BUT IF SINGLE METER | | AN RPZV BACKFLOW WILL BE REQUIRED ON THE | | WATER SERVICE. PLEASE CLARIFY. SECTION | | 608.13.2. | | 3. SHTS P2.2.4, & P3.2.4 SANT. RISERS | | AND FLOOR PLANS FOR UNIT A ANDUNIT B. | | RISERS DO NOT REFLECT THE FLOOR PLANS, | | AND, AS SHOWN, KITCHEN SINK ARMS ARE RUN | | IN FRONT OF THE RANGE ABOVE THE FLOOR. | | PLEASE CLARIFY. SECTION 104.2.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|