2006-06-19 00:00:00PROVISO;2001 FBC/BUILDING 3/6 UNITS
 RESPONSE TO COMMENTS DATED 2-7-06
  
 COMMENT #5:PLAN SHEET M0.1 THE AHU
 MOUNTING DETAIL KEYNOTE DETAIL 15 STATES
 NO COMBUSTIBLES ALLOWED IN THE RETURN
 AIR PLENUM.THE ARCHITECURAL PLANS
 (A-4.0.2) THE DOOR SCHEDULE INDICATES
 "WOOD LOUVERD DOOR".PLEASE VERIFY WITH
 THE DOOR MANUFACTURE THAT THIS DOOR &
 FRAME WILL MEET THE 25 FLAME/50 SMOKE
 INDEX WHEN TESTED UNDER ASTM 84.
  
 COMMENT #6:BOOSTER FANS ARE TO BE
 REMOVED AND SPECIFIC DRYERS ARE TO BE
 INSTALLED.PLEASE NOTE, SPECIFIC DRYERS
 ARE TO BE INSTALLED AT FINAL INSPECTION.
  
 COMMENT #7:PLAN SHEET M0.1. O.A.
 CALCULATIONS ARE BASED ON "INFILTRATION
 RATES".THESE ARE MAXIMUM RATES ALLOWED
 BY THE CODE & MAY NOT BE "ACTUAL/TRUE"
 RATES.THE ACTUAL RATE IS NOT KNOWN
 UNLESS TESTED.O.A. CALCS ARE IN
 ACCORDANCE WITH 2001 FMC 402.2, 402.2.1
 OR TABLE 403.3. PLAN SHEET M2 INDICATESA
 6" O.A. DUCT, PLEASE REMOVE IF THIS IS
 NOT GOING TO BE UTILIZED.
  
 PLEASE REVISE PLANS TO REFLECT THE
 IMPLEMENTATION OF PROVISO'S.
  