Plan Review Notes
Plan Review Notes For Permit 05090886
Permit Number 05090886
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-15 00:00:00***** NOTES REDLINED *******
  
 ** PLANS MUST BE REVISED IF PLANS COME
 BACK FOR ANY OTHER COMMENTS FROM OTHER
 TRADES. IF ALL REVIEWS PASS, THEN PLANS
 ARE TO BE REVISED "BEFORE SLAB
 INSPECTION">
  
  
 ** PLEASE SEE NO, SERVICE ENTRANCE
 CONDUIT OR SERVICE ENTRANCE CONDUCTORS
 ARE SHOWN ON RISER FROM FPL TO 1000A
 SERVICE MAIN.
 PLEASE SEE SEC'S ARE NOTED IN FAULT
 CURRENT CALCS ONLY.
  
 ** PLEASE SEE #4 GEC SHOWN, WHERE A 3/0
 MIN IS REQUIRED PER 250.66.
  
 ** PLEASE SEE 424.3B FOR MIN OCP SHALL
 BE 125% FOR AHU'S. PLEASE SEE OCP HAS
 NOW BEEN DECREASED TO 40A'S???
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-05-14 00:00:00NOTES TO FOLLOW ON 5/15