Date |
Text |
2006-06-19 00:00:00 | DENIED |
| |
| 1) THE PLANS MUST BE STAMPED BY PALM |
| BEACH COUNTY FOR IMPACT FEES. THE PLAN |
| REVIEW NUMBER ON THE PLANS MUST |
| CORRESPOND WITH THE P.R. NUMBER ON THE |
| IMPACT FEE RECEIPT. |
| |
| 2) SUBMIT FIRE SPRINKLER PLANS FOR THE |
| REQUIRED NFPA 13 SYSTEM. THIS IS |
| REQUIRED BY FBC 104.3.1.1 OF THE CITY OF |
| W.P.B. AMENDMENTS TO THE 2001 FBC. |
| |
| 3) THE GARAGE FLOOR/CEILING ASSEMBLY IN |
| DETAIL 17 ON A 10.0.0 DOES NOT |
| CORRESPOND TO THE FC 5517 FIRE RATED |
| ASSEMBLY LISTED IN THE GYPSUM |
| ASSOCIATION MANUAL. PLEASE CORRECT. |
| |
| 4) NUMBER 20 ON THE DOOR SCHEDULE |
| SPECIFIES A VENTED GARAGE DOOR. THE |
| PRODUCT APPROVAL FOR THE GARAGE DOOR |
| DOES NOT INDICATE VENTS IN THE DOOR. |
| |
| 5) REVISE DETAIL 11 ON A 10.0.0 TO |
| SPECIFY THE 2001 FBC AND NOT THE CURRENT |
| EDITION OF THE STANDARD BUILDING CODE. |
| |
| 6) THE DRAWINGS ATTACHED TO THE STATE |
| PRODUCT APPROVAL FOR THE STEEL DOOR FROM |
| MASONITE INTERNATIONAL ARE FOR A 6'-8" |
| DOOR AND THE PLAN SPECIFIES AN 8'-0" |
| DOOR. SEE FL 4940.3 AND DRAWING |
| DWG-MA-FLO 133-05. |
| |
| 7) SUBMIT PRODUCT APPROVALS FOR THE |
| TRUSS CONNECTORS. (SIMPSON-HETAL 12 & |
| 16, USP-USC) THE FL COVERSHEET SUBMITTED |
| FOR THE USP HANGERS AND COLUMN BASES & |
| CAPS HAS A WINDOW MULLION NOA ATTACHED |
| TO IT. |
| |
| 8) THE MIAMI-DADE NOA FOR THE SINGLE |
| HUNG WINDOWS IS INCOMPLETE. THERE ARE |
| SHEETS WITH ANOTHER NOA NUMBER ATTACHED |
| AT THE REAR OF THE SH WINDOW NOA. |
| |
| 9) THE DECORATIVE BAHAMA SHUTTERS WILL |
| REQUIRE A SEPARATE PERMIT. |
| |
| 10) FS 713.13 IF THE IMPROVEMENT |
| DESCRIBED IN THE NOTICE OF COMMENCEMENT |
| IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE |
| IS VOID AND OF NO FURTHER EFFECT. |
| (THE NOC WILL NEED TO BE RE-RECORDED |
| BEFORE THE PERMIT IS ISSUED.) |
| |
| 11) FBC 13-600.3ABC.1.2 REQUIRES THE |
| ENERGY CALCULATION FORMS TO BE SIGNED |
| AND SEALED BY AN ARCHITECT OR AN |
| ENGINEER. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |