Plan Review Notes
Plan Review Notes For Permit 05090886
Permit Number 05090886
Review Stop P
Sequence Number 1
Notes
Date Text
2005-11-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHTS P2.1.1, P-2.2.4, P-3.1.1, P-3.2
 AND P-3.2.4 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINES OF ALL
 UNITS. PER SECTION 604.9. - ALL WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE",
 NOT IN THE CEILING AS SHOWN IN SOME
 CASES. PDI-WH 201 AND MANUF INSTALLATION
 INSTRUCTIONS.
 2. IF INDIVIDUAL METERS NO BACKFLOW
 DEVISE IS REQUIRED, BUT IF SINGLE METER
 AN RPZV BACKFLOW WILL BE REQUIRED ON THE
 WATER SERVICE. PLEASE CLARIFY. SECTION
 608.13.2.
 3. SHTS P2.2.4 & P3.2.4 SANT. RISERS AND
 FLOOR PLANS FOR UNITS A & B. RISER DO
 NOT REFLECT THE FLOOR PLAN, AND AS
 SHOWN, KITCHEN SINK ARMS ARE RUN IN
 FRONT OF THE RANGE ABOVE THE FLOOR.
 PLEASE CLARIFY. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved