Plan Review Notes
Plan Review Notes For Permit 05090886
Permit Number 05090886
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-07 00:00:00DENIED:BUILDING 2 / 2001 FBC
 6 UNITS
 1.PLAN SHEET A-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED, SPRINKLERED.PLEASE
 INDICATE WHICH SYSTEM WILL BE UTILIZED
 (13, 13R, 13D?).PLEASE NOTE,
 ADDITIONAL COMMENTS MAY BE GENERATED BY
 THE RESPONSES GIVEN.
  
 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND,
 ITEM #25 '1HR CHASE REFER TO 11/A-13'.
 PLAN SHEET A-13 WAS NOTE SUBMITTED FOR
 REVIEW.
  
 3.PLEASE CLARIFY FIRE RATING OF THE
 WALL SEPARATING THE GARAGE & THE
 RESIDENCE, DOES THE RATING CONTINUE TO
 THE SLAB OR THE RATED CEILING?
  
 4.PLAN SHEET M1 INDICATES SUPPLY &
 EXHAUST DUCT PENETRATING A RATED WALL.
 DUCT SHALL COMPLY WITH 2001 FMC 607.1.3
 #3 ITEMS 1 THROUGH 4.
  
 5.PLAN SHEET M2 INDICATES DRYER
 EXHAUST GOING THROUGH THE AHU CLOSET
 WHICH APPEARS TO BE A PLENUM.PER 2001
 601.3 EXHAUST DUCT OR VENTS SHALL NOT
 EXTEND INTO OR PASS THROUGH A PLENUM.
  
 6.DRYER EXHAUST EXCEEDS 25FT MAXIMUM
 WITH THE REDUCTION FOR 90'S.PLAN SHEET
 E2.2 INDICATES 'BF' (BOOSTER FAN?).
 PLEASE NOTE, INSTALLATION OF DRYER
 BOOSTER FANS WILL BE REVIEWED BY THE
 BUILDING OFFICIAL UNDER "ALTERNATE
 MATERIALS & METHODS" 2001 FMC 103.7.1.
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.1) A LETTER FROM AN
 ENGINEER EMPLOYED BY THE DRYER
 MANUFACTURER STATING THE INSTALLATION OF
 THE BOOSTER FAN IS ACCEPTABLE AND WILL
 NOT VOID THE WARRANTY OF THE DRYER.2)
 MEANS OF NOTIFYING THE OWNER SHOULD THE
 BOOSTER FAN FAIL.3) MANUFACTURER'S
 SUBMITTAL & INSTALLATION DATA FOR THE
 BOOSTER FAN.4) PROVIDE ALL PERTINENT
 INFORMATION FOR ALL TRADES MECHANICAL,
 ELECTRICAL, FIRE, ETC. FOR THE
 INSTALLATION OF BOOSTER FANS.
  
 7.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER TABLE 403.3 OF THE 2001
 FMC.
  
 8.PLEASE PROVIVDE DETAIL OF THE AHU
 LOCATED IN THE CLOSET.PLEASE NOTE,
 MECHANICAL CLOSET SHALL BE CONSTRUCTED
 PER 2001 FMC 603.9.NO COMBUSTIBLES
 ALLOWED IN THE RETURN AIR PLENUM PER
 2001 FMC 602.2.1.
  
 9.PLEASE PROVIDE DETAIL FOR THE
 ANCHORING OF THE CONDENSING UNIT PER
 2001 FMC 301.13.
  
 10. R/A TRANSFER GRILLES SHALL BE SIZED
 IN ACCORDANCE WITH 2001 FMC 601.4
 EXCEPTION 2 & 3, THIS IS A REQUIRED
 MINIMUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.