Plan Review Notes
Plan Review Notes For Permit 05090882
Permit Number 05090882
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-14 00:00:00 
 1) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2) THE AWNING SHALL BE DESIGNED TO THE
 140MPH BASIC WIND SPEED WITH THE COVER
 IN PLACE.SEE F.B.C SEC.1606.1.6 AND
 1606.1.7.
  
 3) WHAT TYPE OF STRUCTURE WILL THE
 AWNING BE ANCHORED INTO? IS IT
 CONCRETE/BLOCK/WOOD OR HOLLOW CLAY TILE?
  
 4)SUBMIT THE CERTIFICATE SHOWING THE
 FLAME SPREAD RATING OF THE AWNING
 MATERIAL.SEE F.B.C SEC.3204.2.
  
 5) SUBMIT A SURVEY OR SITE PLAN SHOWING
 THE SIDEWALK WIDTH. THE FIXED AWNING
 SHALL NOT EXTEND OR OCCUPY NOR THAN
 TWO-THIRDS OF THE SIDEWALK. FBC 3204.3.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX(561)659-8026
 [email protected]
  