2006-08-05 00:00:00 | **********UNSAT *********** |
| |
| 1) NOTE: PLEASE CLARIFY UNDERGROUND |
| SEC'S TO FPL. IF THESE ARE INSTALLED BY |
| FPL , THEN PLEASE DO NOT INDICATE THE |
| CONDUCTOR SIZES, AS THESE WILL NOT |
| CORRELATE WITH FPL. |
| PLEASE ALSO VERIFY THE DOWNSIZING OF THE |
| NEURTRAL CONDUCTOR TO A #3. |
| PLEASE PROVIDE NEUTRAL LOAD CALCULATION |
| OR FULL SIZE NEUTRAL. |
| 220.22, 310.15B6 |
| |
| 2) NOTE: PLEASE SHOW CONDUIT SIZE FOR |
| THE UNDERGROUND AND ALSO THE CONDUIT TO |
| INSIDE PANEL. UNABLE TO VERIFY AT THIS |
| TIME. |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE SEE 210.52C1AS THERE |
| ARE SOME RECEPTS MISSING . SEE REDLINED |
| PLANS. |
| PLEASE SEE AREAS OF COUNTER SPACE, |
| PLEASE SEE LOCATED NEXT TO STOVE ETC. |
| |
| 4) NOTE: PLEASE SEE MISSING ISLAND |
| GFI RECEPT. 210.52C1-5,210.8A6 |
| |
| 5) NOTE: PLEASE SEE THAT ALL ROOM AND |
| AREA DESIGNATIONS ON PLANS CORRELATE |
| WITH THE PANEL SCHEDULE. |
| PLEASE SEE THAT ALL CIRCUITS ON PANEL |
| SCHEDULE SHALL BE SPECIFIC TO ROOMS AND |
| AREAS. |
| IE; LIVING RM RECEPTS, BEDRM #2 |
| LTS/RECEPTS, HALL LTS ETC ETC. |
| 408.4 FBC 106.1.2 |
| **IT IS KNOWN THAT CIRCUITING DURING |
| CONSTRUCTION WILL CHANGE AND THIS CAN EB |
| REVISED AT A LATER DATE. |
| |
| 6) NOTE: PLEASE SEE ONLY TWO CIRCUITS |
| ARE BEIGN SHOWNWITH ARC FAULT |
| PROTECTION FOR ALL BEDRMS LTS, RECEPTS |
| AND SD'S. PLEASE KNOW, THE CODE HAS |
| CHANGED FROM PREVIOUSLY SUBMITTED PLANS |
| UNDER THIS PROJECT TO REQUIRE ARC FAULT |
| PROTECTION FOR ALL OUTLETS IN BEDRMS. |
| PLEASE BE SURE TO REVISE AS THE LOAD ON |
| THESE ONLY TWO CIRCUITS SEEM TO EXCEED |
| RATINGS. |
| 210.12B(2002) NEC. 210.52,220 |
| |
| 7)NOTE: PLEASE SEE MISSING THE REQUIRED |
| DEDICATED BATH(S) CIRCUIT(S). |
| 210.11C3, SHALL BE 20A AND #12. |
| NO BATH(S) LISTED. |
| |
| 8) NOTE: PLEASE BE SURE HE PLANS PROVIDE |
| THE FOLLOWING MINIMUM CODES AS ADOPTED |
| FOR DESIGN AND FS/FBC 2004 |
| 2002 NFPA-70, 2002 NFPA-72, 2003 |
| NFPA-101. |
| |
| 9) NOTE: PLEASE SEE PLANS INDICATE THE |
| PANEL LOCATED INHALL ON PLANS AND |
| PANEL SCHEDULE SAY HALL/UTILITY.?? |
| PLEASE SEE ELECTRICAL PLANS DO NOT SHOW |
| THE SAME WALL AS SHOWN ON BUILDING |
| PLANS. |
| PLEASE ALSO CLARIFY THE MISSING CONTROL |
| FOR LT(S) IN THE UTILITY RM. 210.70 |
| |
| 10) NOTE: PLEASE SEE "J-BOXES" SHOWN ON |
| PLANS NEED TO BE NOTED FOR "FUTURE FAN |
| BOXES' IF INDEED FOR FANS. PLEASE SEE |
| 314.47D |
| |
| 11) NOTE: PLEASE SEE PLANS DO NOT SHOWN |
| LOCATION OF SERVICE ON THE OUTSIDE OF |
| HOUSE. |
| 106.1.2 |
| |
| 12) NOTE: PLEASE SEE SURVEY PROVIDED IN |
| PACKAGE IS REQUIRED TO CONTAIN AN |
| ORIGINAL SIAGNAURE IN ORDER FOR SURVEY |
| TO BE VALID. PLEASE SEE FAC 61G15-17, FS |
| 472.025 |
| |
| 13) NOTE: PLEASE SEE MISSING THE DINING |
| ROOM CIRCUITS ON ONE OR MORE OF THE SM |
| APPL CIRCUITS. 210.11C1,220.16 |
| |
| 14) NOTE: PLEASE SEE DISHWASHER AND |
| DISPOSAL SEEM TO BE SHARED TO THE SAME |
| RECEPT, HOWEVER PLEASE SEE PANEL DOES |
| NOT INDICATE A 2-POLE BREAKER. PLEASE |
| SEE 210.4B |
| |
| 15) NOTE: PLEASE SEE MISSING DISCONNECT |
| AND GROUNDING AT THE DETACHED BLDG. |
| PLEASE SHOW ON ELECTRICAL PLANS. |
| PLEASE REVISE PANEL SCHEDULES AND LOAD |
| CALCS. |
| PLEASE SEE 225.31-225.39, 250.32 |
| |
| ** IMPORTANT ** |
| BEFORE RESUBMITTING PLANS ONCE ALL |
| REVIEWS ARE COMPLETED. PLEASE BE SURE TO |
| COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT THE NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| ONLY ONE COPY OF THE OLD SHEETS SHOULD |
| BE SUBMITTED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |