2006-08-05 00:00:00**********UNSAT ***********
  
 1) NOTE: PLEASE CLARIFY UNDERGROUND
 SEC'S TO FPL. IF THESE ARE INSTALLED BY
 FPL , THEN PLEASE DO NOT INDICATE THE
 CONDUCTOR SIZES, AS THESE WILL NOT
 CORRELATE WITH FPL.
 PLEASE ALSO VERIFY THE DOWNSIZING OF THE
 NEURTRAL CONDUCTOR TO A #3.
 PLEASE PROVIDE NEUTRAL LOAD CALCULATION
 OR FULL SIZE NEUTRAL.
 220.22, 310.15B6
  
 2) NOTE: PLEASE SHOW CONDUIT SIZE FOR
 THE UNDERGROUND AND ALSO THE CONDUIT TO
 INSIDE PANEL. UNABLE TO VERIFY AT THIS
 TIME.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE 210.52C1AS THERE
 ARE SOME RECEPTS MISSING . SEE REDLINED
 PLANS.
 PLEASE SEE AREAS OF COUNTER SPACE,
 PLEASE SEE LOCATED NEXT TO STOVE ETC.
  
 4) NOTE: PLEASE SEE MISSING ISLAND
 GFI RECEPT. 210.52C1-5,210.8A6
  
 5) NOTE: PLEASE SEE THAT ALL ROOM AND
 AREA DESIGNATIONS ON PLANS CORRELATE
 WITH THE PANEL SCHEDULE.
 PLEASE SEE THAT ALL CIRCUITS ON PANEL
 SCHEDULE SHALL BE SPECIFIC TO ROOMS AND
 AREAS.
 IE; LIVING RM RECEPTS, BEDRM #2
 LTS/RECEPTS, HALL LTS ETC ETC.
 408.4 FBC 106.1.2
 **IT IS KNOWN THAT CIRCUITING DURING
 CONSTRUCTION WILL CHANGE AND THIS CAN EB
 REVISED AT A LATER DATE.
  
 6) NOTE: PLEASE SEE ONLY TWO CIRCUITS
 ARE BEIGN SHOWNWITH ARC FAULT
 PROTECTION FOR ALL BEDRMS LTS, RECEPTS
 AND SD'S. PLEASE KNOW, THE CODE HAS
 CHANGED FROM PREVIOUSLY SUBMITTED PLANS
 UNDER THIS PROJECT TO REQUIRE ARC FAULT
 PROTECTION FOR ALL OUTLETS IN BEDRMS.
 PLEASE BE SURE TO REVISE AS THE LOAD ON
 THESE ONLY TWO CIRCUITS SEEM TO EXCEED
 RATINGS.
 210.12B(2002) NEC. 210.52,220
  
 7)NOTE: PLEASE SEE MISSING THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S).
 210.11C3, SHALL BE 20A AND #12.
 NO BATH(S) LISTED.
  
 8) NOTE: PLEASE BE SURE HE PLANS PROVIDE
 THE FOLLOWING MINIMUM CODES AS ADOPTED
 FOR DESIGN AND FS/FBC 2004
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101.
  
 9) NOTE: PLEASE SEE PLANS INDICATE THE
 PANEL LOCATED INHALL ON PLANS AND
 PANEL SCHEDULE SAY HALL/UTILITY.??
 PLEASE SEE ELECTRICAL PLANS DO NOT SHOW
 THE SAME WALL AS SHOWN ON BUILDING
 PLANS.
 PLEASE ALSO CLARIFY THE MISSING CONTROL
 FOR LT(S) IN THE UTILITY RM. 210.70
  
 10) NOTE: PLEASE SEE "J-BOXES" SHOWN ON
 PLANS NEED TO BE NOTED FOR "FUTURE FAN
 BOXES' IF INDEED FOR FANS. PLEASE SEE
 314.47D
  
 11) NOTE: PLEASE SEE PLANS DO NOT SHOWN
 LOCATION OF SERVICE ON THE OUTSIDE OF
 HOUSE.
 106.1.2
  
 12) NOTE: PLEASE SEE SURVEY PROVIDED IN
 PACKAGE IS REQUIRED TO CONTAIN AN
 ORIGINAL SIAGNAURE IN ORDER FOR SURVEY
 TO BE VALID. PLEASE SEE FAC 61G15-17, FS
 472.025
  
 13) NOTE: PLEASE SEE MISSING THE DINING
 ROOM CIRCUITS ON ONE OR MORE OF THE SM
 APPL CIRCUITS. 210.11C1,220.16
  
 14) NOTE: PLEASE SEE DISHWASHER AND
 DISPOSAL SEEM TO BE SHARED TO THE SAME
 RECEPT, HOWEVER PLEASE SEE PANEL DOES
 NOT INDICATE A 2-POLE BREAKER. PLEASE
 SEE 210.4B
  
 15) NOTE: PLEASE SEE MISSING DISCONNECT
 AND GROUNDING AT THE DETACHED BLDG.
 PLEASE SHOW ON ELECTRICAL PLANS.
 PLEASE REVISE PANEL SCHEDULES AND LOAD
 CALCS.
 PLEASE SEE 225.31-225.39, 250.32
  
 ** IMPORTANT **
 BEFORE RESUBMITTING PLANS ONCE ALL
 REVIEWS ARE COMPLETED. PLEASE BE SURE TO
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT THE NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONLY ONE COPY OF THE OLD SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  