Plan Review Notes
Plan Review Notes For Permit 05090863
Permit Number 05090863
Review Stop M
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00*** DENIED ***
 1) JOB ADDRESS MUST APPEAR ON ALL PAGES
 OF PLANS.
  
 2) MECHANICAL PLANS EQUIPMENT LIST SHOWS
 AHU IS A 10 SEER AND CONDENSER UNIT IS A
 12 SEER, PLEASE SHOW THE SEER OF THE
 SYSTEM ONLY. AND SHOW THE TOTAL BTU'S.
 AND SENSIBLE BTU'S. OF THE A/C SYSTEM.
  
 3) PLEASE SHOW ON MECH. PLANS THE SIZE
 OF THE RETURN AIR GRILL TO THE AIR
 HANDLER.
  
 4) RETURN AIR TRANSFER DUCTS TO
 BEDROOMS, THE GRILLS ARE TO SMALL FOR
 THE DUCTS.
  
 5) SUPPLY AIR DUCT TO SECOND FLOOR
 CLOSET #2 NEEDS TO BE SIZED.
  
 6) PLEASE EXPLAIN WHY A 7" SUPPLY AIR
 DUCT IS GOING TO THE SMALL CLOSET IN THE
 HALL.
  
 7) PLEASE SUBMIT MANUAL D CALCULATIONS
 FOR RESIDENTIAL DUCT DESIGN, PER 2004
 FBC/R M1601.1 AND FBC 13-610.1.ABC.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.