Plan Review Notes For Permit 05090851 |
Permit Number |
05090851 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-30 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE APPLIED VALUE MUST INCLUDE ALL | | COSTS FOR EQUIPMENT AND LABOR. SEE | | 104.2.1 FBC. INCREASE THE VALUE ON THE | | APPLICATION AND PAY FEES ACCORDINGLY AT | | TIME OF RESUBMITTAL. | | | | 2} PLEASE INDICATE WHICH MODEL GENERATOR | | IS INTENDED TO BE INSTALLED SO THEAT THE | | PROPER SPEC'S MAY BE REVIEWED. THERE ARE | | THREE ON THE SHEETS SUBMITTED. | | | | 3} PLEASEW SEE THAT THE LIGHTING LOAD | | CALCULATION GIVEN WOULD INDICATE A 333 | | SQ FT. HOUSE. SEE TABLE 220.3(A). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | | | |
|