Plan Review Notes
Plan Review Notes For Permit 05090826
Permit Number 05090826
Review Stop B
Sequence Number 5
Notes
Date Text
2007-03-02 19:03:50BUILDING REVISION THIRD CHECKLIST:
 1- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS IF
 WORK IS NOT STARTED. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 2- BRING DRAWINGS TO PALM BEACH COUNTY FOR IMPACT FEES
 REVISION. BRING BACK STAMPED DRAWINGS AND PAID RECEIPT
 IF ADDITIONAL FEES ARE DUE.
  
 3- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
  
 4- OWES $788.35 FOR UPDATED PERMIT VALUATION AND RADON
 FEES.
 ***NOTE: FEES TO BE PAID AT TIME OF NEXT SUBMITTAL.
 PLAN REVIEW WILL NOT BE DONE UNTILALL FEES ARE PAID.
  
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON
 ARCHITECT'S PLANS.
  
 6- ARCHITECT TO PROVIDE THE FIRM LICENSE NUMBER AS
 REQUIRED BY SEC. 61G1-16.004 OF FLORIDA ADMINISTRATIVE
 CODE.
  
 7- CLARIFY WHY IS ARCHITECT APPROVING PRODUCT APPROVAL
 FOR 4", 6" AND 12" CONCRETE LINTELS IF THERE ARE NO
 SUCH TYPE OF LINTELS SPECIFIED ON PLANS.
  
 8- NEED TO ADDRESS ELECTRICAL COMMENTS ALSO. ***NOTE:
 WHEN RE-SUBMITTING MAKE SURE PROPER PLAN REVIEW TRADES
 ARE INDICATED ON THE RE-SUBMITTTAL FORM TO EXPEDITE THE
 REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712