Date |
Text |
2007-01-22 14:04:37 | BUILDING REVISION SECOND CHECKLIST (REVISION DONE UNDER |
| FBC 2004 AS SPECIFIED ON PLANS): |
| 1- TRUSS DRAWINGS WILL BE REQUIRED FOR REVIEW PRIOR TO |
| INSTALLATION. SEE SEC. R802.10 FOR REQUIRED |
| INFORMATION. DESIGNER OF RECORD TO REVIEW AND APPROVE |
| THEM PRIOR TO SUBMITTAL TO THIS OFFICE. |
| |
| 2- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF |
| BEING RECORDED IF WORK IS NOT STARTED. SEC. 713.13(2) |
| FLORIDA STATUTES. NEED RE-RECORDED NOTICE OF |
| COMMENCEMENT. |
| |
| 3- A) REVISE THE ENERGY CALCULATIONS. OVERHANG LENGTH |
| AND OVERHANG HEIGHT ARE INCORRECT. |
| |
| B) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| |
| 4- BRING DRAWINGS TO PALM BEACH COUNTY FOR IMPACT FEES |
| REVISION. BRING BACK STAMPED DRAWINGS AND PAID RECEIPT |
| IF ADDITIONAL FEES ARE DUE. |
| |
| 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS |
| UNDER A SEPARATE PERMIT AS AGREED ON AT TIME OF |
| ORIGINAL PERMIT APPLICATION APPROVAL. |
| |
| 6- OWES $788.35ADDITIONAL FEES FOR UPDATED BUILDING |
| VALUATION,RADON FEES AND REVISION FEES.. |
| |
| 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| FOR: |
| A) INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| B) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON |
| PLANS. |
| C) PRECAST CONCRETE LINTELS AS SPECIFIED ON PLANS. |
| D) ALL SIMPSON OR USP CONNECTORS SPECIFIED ON |
| FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA |
| PRODUCT APPROVAL COVER PAGE AND THE SPECIFIC PAGE |
| SHOWING THE CONNECTOR. |
| E) SINGLE HUNG WINDOWS. |
| |
| 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| PRODUCT APPROVAL FOR TIBERLINE SHINGLES IS MISSING THE |
| ARCHITECT'S SIGNATURE. |
| |
| 9- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S |
| INFORMATION AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| ADMINISTRATIVE CODE. MISSING THE FIRM'S NUMBER. |
| |
| 10- SHEET A-2.1: |
| A) FLOOR PLAN CALLS FOR ONE 16'X7' GARAGE DOOR. |
| ELEVATION SHOWS 2 SMALL GARAGE DOORS.PRODUCT APPROVAL |
| FOR GARAGE DOORS DON'T SHOW DOOR TO LOOK LIKE 2 DOORS |
| IN ONE. HOW IS THIS ACHIEVED. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004 |
| |
| 11- SHEET S-2: |
| A) DETAIL 1/S-2 CALLS FOR (3)2X4 STUDS, WHILE 2ND |
| FLOOR FRAMING PLAN CALLS FOR (4)2X4 STUDS. |
| CLARIFY/REVISE AS REQUIRED TO MATCH. |
| |
| 19- SHEET S-3: |
| A) REVISE PLYWOOD SHEATHING NAILING SCHEDULE FOR |
| ROOF SHEATHING AT ZONE 3. SEE TABLE 2304.9.1 FBC 2004 |
| AND REVISE AS REQUIRED. |
| |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |