Plan Review Notes For Permit 05090826 |
Permit Number |
05090826 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-01-18 11:22:31 | PROVISO: | | 1.PER 2004 FRC M1602.4, PRESSURE DIFFERENTIALS ACROSS | | CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL | | BE LIMITEDTO .01 INCH WC (2.5 PASCALS) OR LESS. | | | | 2.FOR PROPER SIZING OF RETURN AIR FROM THE MATER | | SUITE, ALL AIR SUPPLY INTO THE MASTER SUITESHALL BE | | INCLUDED FOR TOTAL SUPPLY AIR (INCLUDE SUPPLY AIR TO | | CLOSETS, BATHROOM, ETC) AND SIZE RETURN ACCORDINGLY. | | 2004 FRC M1602.4 EXCEPTION 1 AND 3.TEST AND BALANCE | | REQUIRED FOR FINAL INSPECTION. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW PROTECTION | | REQUIRED PER 2004 FRC M1411.3.1. | | | | 4.A MINIMUM OF 4" CLEARANCE AROUND THE AHU IS | | REQUIRED IN ACCORDANCE WITH 2004 FBC CHAPTER 13 | | SUB-CHAPTER 13-610.1.ABC.3.0.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|