Plan Review Notes
Plan Review Notes For Permit 05090826
Permit Number 05090826
Review Stop E
Sequence Number 3
Notes
Date Text
2006-08-10 00:00:00**********UNSAT ***********
  
 1) NOTE: PLEASE CLARIFY UNDERGROUND
 SEC'S TO FPL. IF THESE ARE INSTALLED BY
 FPL , THEN PLEASE DO NOT INDICATE THE
 CONDUCTOR SIZES, AS THESE WILL NOT
 CORRELATE WITH FPL.
 PLEASE ALSO VERIFY THE DOWNSIZING OF THE
 NEURTRAL CONDUCTOR TO A #3.
 PLEASE PROVIDE NEUTRAL LOAD CALCULATION
 OR FULL SIZE NEUTRAL.
 220.22, 310.15B6
  
 2) NOTE: PLEASE SHOW CONDUIT SIZE FOR
 THE UNDERGROUND AND ALSO THE CONDUIT TO
 INSIDE PANEL. UNABLE TO VERIFY AT THIS
 TIME.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE 210.52 AS THERE ARE
 SOME RECEPTS MISSING . SEE REDLINED
 PLANS.
 PLEASE SEE AREA OF WALL OFF KITCHEN AND
 WHAT APPEARS TO BE THE MASTER BEDRM.
  
 4) NOTE: PLEASE SEE MISSING PENINSULAR
 GFI RECEPT. 210.52C3,210.8A6
  
 5) NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS AND CORRELATE
 WITH THE PANEL SCHEDULE.
 PLEASE SEE THAT ALL CIRCUITS ON PANEL
 SCHEDULE SHALL BE SPECIFIC TO ROOMS AND
 AREAS.
 IE; LIVING RM RECEPTS, BEDRM #2
 LTS/RECEPTS, HALL LTS ETC ETC.
 408.4 FBC 106.1.2
 **IT IS KNOWN THAT CIRCUITING DURING
 CONSTRUCTION WILL CHANGE AND THIS CAN EB
 REVISED AT A LATER DATE.
  
 6) NOTE: PLEASE SEE ONLY TWO CIRCUITS
 ARE BEIGN SHOWNWITH ARC FAULT
 PROTECTION FOR ALL BEDRMS LTS, RECEPTS
 AND SD'S. PLEASE KNOW, THE CODE HAS
 CHANGED FROM PREVIOUSLY SUBMITTED PLANS
 UNDER THIS PROJECT TO REQUIRE ARC FAULT
 PROTECTION FOR ALL OUTLETS IN BEDRMS.
 PLEASE BE SURE TO REVISE AS THE LOAD ON
 THESE ONLY TWO CIRCUITS SEEM TO EXCEED
 RATINGS.
 210.12B(2002) NEC. 210.52,220
  
 7)NOTE: PLEASE SEE MISSING THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S).
 210.11C3, SHALL BE 20A AND #12.
 NO BATH(S) LISTED.
  
 8) NOTE: PLEASE BE SURE HE PLANS PROVIDE
 THE FOLLOWING MINIMUM CODES AS ADOPTED
 FOR DESIGN AND FS/FBC 2004
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101.
  
 9) NOTE: PLEASE SEE PLANS INDICATE THE
 PANEL LOCATED IN GARAGE, YET PANEL
 MENTIONS THIS IN HALL/UTILITY.
  
 10) NOTE: PLEASE SEE MIN EGRESS LIGHTING
 IS REQUIRED FOR WHAT APPEARS TO BE
 DINGIN AND LIV RM FOR EGRESS. SHOWS ONLY
 A JUNCTION BOX FOR FUTURE FAN. PLEASE
 KNOW, THIS CAN BE EITHER PROVIDED BY THE
 SWITCHING OF A RECEPT OR A LT FIXTURE OF
 SOME TYPE WHICH SHALL BE PROIVIDED.
 210.70, LS101 7.8
  
 11) NOTE: PLEASE SEE PLANS SHOWS A METER
 AND A MAIN DISCONNECT ON THE OUTSIDE. IF
 THIS IS THE CASE, PLEASE REVISE RISER TO
 INCLUDE THIS MAIN AND ALSO INCLUDE
 EQUIPMENT GROUNDING CONDUCTORS AS
 REQUIRED.
 250.24B, 250.122
 106.1.2
  
 12) NOTE: PLEASE SEE SURVEY PROVIDED IN
 PACKAGE IS REQUIRED TO CONTAIN AN
 ORIGINAL SIAGNAURE IN ORDER FOR SURVEY
 TO BE VALID. PLEASE SEE FAC 61G15-17, FS
 472.025
  
 13) NOTE: PLEASE SEE MISSING THE DINING
 ROOM CIRCUITS ON ONE OR MORE OF THE SM
 APPL CIRCUITS. 210.11C1,220.16
  
 14) NOTE: PLEASE SEE 210.4B AS THE
 DISHWASHER/DISPOSAL ARE FROM THE SAME
 RECEPT, HOWEVER THESE ARE ON 1-POLE
 BREAKERS. THIS REQUIRES A 2-POLE BRKR.
  
 15) NOTE: PLEASE SEE COUNTER SPACE IN
 KTICHEN AS IT SEEMS IT IS MISSING GFI
 RECEPT(S). PLEASE SEE 210.52C1 AND
 REDLINED PLANS.
  
 16) NOTE: PLEASE SEE "S" SHEETS AS THESE
 ARE MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER FOR ENGINEERING
 FIRM.
 FAC 61G15-23.002, FS 471.023
  
 ** IMPORTANT **
 BEFORE RESUBMITTING PLANS ONCE ALL
 REVIEWS ARE COMPLETED. PLEASE BE SURE TO
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT THE NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONLY ONE COPY OF THE OLD SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved